3.1 Seasonal Statistics
The daily cycle of the 10 m wind speed and the 2 m temperature, relative humidity and dew point temperature were computed in the six weather stations during the summer period. This data provides both the average and the extreme values (depending on the variable), hence gives an insight on the intraday variability and the full range of the observed values.
The daily cycle of the 2 m temperature (
Figure 2) shows that it is more pronounced in the valley and decreases with elevation. During the daytime, the average values decrease with increasing altitude, except in the two AWS with highest elevations (Trevim - 1167 m and Penhas Douradas - 1380 m), which may be attributed to local effects. During the nighttime Seia shows the lowest 2 m temperature average of all the sites and Lousã has similar values to stations with elevations around 600-900 m. The lowest 2 m temperatures were observed in the stations with higher elevations and in Seia, with values around 4°C. The highest 2 m temperature values occurred in the afternoon, with the valley stations reaching at least 40°C and around 32-34°C at elevations above 1200 m. During the nighttime the highest values were observed in Candal (621 m asl).
The daily cycle of the 2 m relative humidity (
Figure 3) shows a large range in the valley stations. The average values are the highest during nighttime (around 90%) and the lowest 40-60% during daytime (40-60%), in the valley stations and in the highest elevation site (Penhas Douradas). In the remaining sites the range of the diurnal cycle typically decreases with increasing elevation. Overall, the average values of 2 m relative humidity decrease with increasing elevation during nighttime. During daytime the minimum values of relative humidity were similar in all sites, with values below 20%, while in the nighttime the lowest values were observed in the stations with the highest elevations, with observations as low as 5-10%.
The average values of 2 m dew point temperature (
Figure S1) decrease as the altitude increases and the daily cycle of the AWS installed at higher elevations has a higher range than the one observed in the valley stations. The minimum values of 2 m dew point temperature were observed during the nighttime on the ridge, with values around -20°C above 1200 m asl. On the other hand, in these sites there is a sharp increase in the minimum values during daytime, which is likely due to the strong vertical mixing in the afternoon.
The daily cycle of the 10 m wind speed shows that it typically increases with altitude (
Figure 4) and that the highest average values are observed in the afternoon, usually between 15 and 18 UTC. In Penhas Douradas there is a lag, hence the highest average values are observed in the evening. Given its location in a sheltered and narrow valley, Candal has the lowest average values of 10 m wind speed and does not show a discernible daily cycle. The minimum values of 10 m wind speed in all sites are below 1 m/s (not shown), while the maximum values are observed in the AWS on the ridge and upper slope. In Penhas Douradas and Trevim the maximum values are observed during nighttime, while the opposite is observed in the valley stations. Therefore, the average wind shear between the AWS in the valley and the ridge is higher during nighttime and lowest during daytime.
The wind roses (
Figure 5), shown only in selected weather stations, provide an overview of the observed prevailing wind direction (and the associated wind speed) from the mountain ridge (Penhas Douradas and Trevim) to the valley (Seia). In the middle slope, Candal is also presented because of its unique location.
In Penhas Douradas the wind directions with the highest frequencies are west/northwest and southeast, while in Trevim are from the west and northeast. This result highlights the strong influence of the topography as both stations are located on the ridge. In Seia the wind speed is mainly below 4 m/s and the most frequent directions are west/southwest, which shows that the flow is predominantly along the main orientation of the Lousã/Estrela mountain range (southwest/northeast). In Candal the wind speed is the lowest and there is a high frequency of northern/southern winds, which may be evidence of a thermal circulation (slope winds). The other two directions with the highest frequencies are parallel to the orientation of the narrow valley where the AWS is installed.
In summer the wind breeze is a prevailing feature of the weather in mainland Portugal and
Figure S2 shows an example of its progression inland during the afternoon. The effect of this mesoscale circulation is seen in the daily cycle of the wind direction (
Figure 6), namely when assessing the frequency of westerly and non-westerly winds. In all AWS, except Penhas Douradas, westerly winds have a frequency below 30% during the nighttime. This frequency increases during the day, with values reaching 70-90% in the period 16-18 UTC, after which they drop rapidly in the evening.
Even though most of the sites exhibit a similar pattern, Candal shows a faster transition of the prevailing wind direction during the morning, which leads to a frequency of westerly winds around 80% from 10 UTC onwards. In Penhas Douradas the daily cycle is the least pronounced, as the frequency of westerly winds is already high during nighttime, around 40-50%. This site also exhibits a lag, when compared to the other AWS, regarding the timing of the increase of the frequency of westerly winds in the morning.
3.2 Vertical variability: timeseries overview
From the hourly observed data in the AWS, the timeseries of the differences in the meteorological variables were computed in the nighttime period. A filter was applied to the data as only dry days were considered, according to the definition in section 2.3. The differences are computed for distinct layers, starting from the two stations located at higher elevations down to the valley. The stations used are Penhas Douradas and the ones installed in the Lousã region. In spite Lousã and Seia regions are 60 km apart, as the observed weather conditions are similar in the whole area, the weather station in Espinheiro is also used to increase the number of vertical layers. Given that Seia is in a valley and the data from this AWS showed that a strong surface inversion is a common feature, this site was disregarded in this section.
The vertical variability in the Lousã/Seia region is assessed by the vertical gradient and the difference between the observed data at four different layers. In the case of the 2 m temperature, in 90% of the cases the differences between the sites with an altitude above 995 m asl are, approximately, comprised between +/-2°C/100 m, but the extreme values may exceed +/-3.5°C/100 m (
Figure 7a). In the layers with AWS with elevations below 995 m, the vertical gradient is smaller and the difference between the extremes of the distribution and the percentiles 5 and 95 is lower. The differences in the 2 m temperature may exceed +/-5°C in all the layers (
Figure 7b). Considering all the layers, the maximum difference observed was recorded between Candal and Lousã, with a value exceeding 9°C.
The variability of the 2 m relative humidity is higher in the layers with weather stations above 995 m asl, when compared to the lower ones (
Figure 8a). At higher levels the vertical gradient may reach -40%/100 m, while in the layer Trevim-Espinheiro it may attain values close to 40%/100 m. The layer Candal-Lousã is the only one where positive values of the vertical gradient are the least frequent. Overall, the differences between the stations may exceed -60% and +40% (
Figure 8b), except for the lower layer, as the difference in 2 m relative humidity in Candal does not exceed a value 18% above the one observed in Lousã.
The vertical variability of the 10 m wind speed drops significantly in the lower two layers and the distributions are less symmetrical than in the other variables (
Figure 9a). While the wind shear between Penhas Douradas and Trevim is comprised between +/-9 m/s (
Figure 9b), positive values are more frequent in the layer immediately below. In the lowest layer the wind shear is the smallest, with the extremes of the distribution comprised between +/-3 m/s. However, in the case of the 10 m wind gust (not shown), which is likely a preferable measure of the turbulence between Candal and Lousã in strong downslope wind events, one finds that it may reach values up to 7 m/s.
A thorough assessment of the timeseries of the differences in the 2 m temperature and relative humidity and 10 m wind speed/gusts (
Figures S3–S6), along with model data from ECMWF-HRES (not shown), shows that large variability in the aforementioned layers occurs in preferred weather conditions. Some of the most significant conclusions are summarized below.
- a)
Between Penhas Douradas (1380 m asl) and Trevim (1167 m asl) there were seven events with a 2 m temperature difference equal or above 5°C. These events occurred with a west/northwesterly flow in both AWS and positive differences in the 10 m wind speed. In these periods, the values of 2 m relative humidity in Penhas Douradas were frequently 40% lower than in Trevim and the extreme minimum differences reached -80%.
- b)
Between Penhas Douradas and Trevim there were 16 events with a 2 m temperature difference equal to or below -5°C. In these periods the wind direction was mainly from the east/southeast aloft and east/northeast in Trevim. The difference in the 10 m wind speed was usually negative, which implies higher values at the lower elevation (Trevim). Given the orientation of the mountain ridge, a strong interaction between the flow and the topography is likely to play a relevant role in such conditions.
- c)
While the data between Trevim (1167 m asl) and Espinheiro (995 m asl) shows a large dispersion, negative differences in the 10 m wind speed only occurred with an east/northeast in Trevim and a southeasterly wind in Espinheiro. The biggest differences in 2 m temperature occurred with south/southwesterly or east/northeasterly winds at both sites. In the latter case large negative differences in the 2 m relative humidity were also observed.
- d)
Despite the large dispersion, the data from Espinheiro (995 m asl) and Candal (621 m asl) shows that positive differences in the 2 m temperature and large negative differences in the 2 m relative humidity (over -40%) occurred with an east/southeasterly flow at the site aloft.
- e)
Large positive differences in the 2 m temperature between Candal (621 m asl) and Lousã (195 m asl) and large negative differences in the 2 m relative humidity (lower or equal to -40%) occurred with east/southeasterly winds in Candal. In these periods the wind direction was from the west/northwest in Lousã. Negative differences in the 2 m temperature were observed with northwesterly winds in Candal.
- f)
In Candal the 10 m wind speed may be higher than in Lousã and this was observed either from the W/NW or E/SE directions, which may suggest channelling in the narrow valley. On some occasions the 10 m wind speed is below 2 m/s in both Candal and Lousã, but the 10 m wind gusts in Candal may exceed by 6 m/s the values observed in the valley. In these events the wind direction is from the E/SE in Candal, which suggest that strong downslope winds do not always reach the valley.
- g)
Differences in the 2 m relative humidity larger than -60% were observed in 15 events in Candal/Lousã and the frequency of temperature inversions was 63%. In the Seia region, the frequency of temperature inversions between the valley station and Espinheiro was higher, at 88%. Both results highlight the large vertical variability between valley areas and the medium slope.
- h)
The frequency of temperature inversions in the upper slope was 50% when using data from Penhas Douradas and Trevim. If a deeper layer is chosen (Penhas Douradas-Espinheiro), the frequency drops to 23%. Finally, the frequency of temperature inversion in all the layers between Penhas Douradas and Candal is lower, at 12%.
- i)
Large negative differences in the 2 m relative humidity (more than -40%) were observed in all the three layers studied between Penhas Douradas and Candal. When these large differences were observed in the two upper layers (Penhas Douradas/Trevim and Trevim/Espinheiro) a strong vertical gradient of the potential temperature was detected in the 880-940 hPa layer. When the large negative difference in 2 m relative humidity was observed between Espinheiro and Candal, the strong vertical gradient was usually around 930-960 hPa. When dry air is detected as low as in Candal, which is taken by considering the threshold of 2°C in the 2 m dew point temperature at this site, an inversion was present at levels below 960 hPa level. Model data tends to overestimate these low values of 2 m dew point temperature in Candal (not shown).