2. Materials and Methods
A rule-based expert system (RBES) is an Artificial Intelligence component that uses knowledge-based rules to perform an activity [
41]. Their design is similar to an advanced computer program that tries to mimic the capabilities of a human expert by collecting knowledge sources used to perform an objective in a particular domain [
38,
41]. Thus, knowledge is taken from the human expert and converted into a production rule set representing the domain knowledge. Their main components are the following: knowledge base module, inference engine, decision-making module, explanation facilities, and user interface.
Figure 2.
The structure of the proposed RBES used in the voltage control from the LV AEDNs.
Figure 2.
The structure of the proposed RBES used in the voltage control from the LV AEDNs.
The knowledge database of the proposed expert system includes two categories: the rule base and the database. The rule base stores rules and facts, while the second, divided into static and dynamic partitions, is associated with recording the immutable facts. The static partition of the database contains information on the features of the LV AEDNs regarding:
line sections characterized by the input and end nodes, type (aerial/underground), cross-sections of the phase, and neutral conductors;
MV/LV distribution transformers from the EDSs characterized by rated power, performance standards identified through the commissioning year, tap changer type (NLTC/OLTC), and tap positions;
reactive power compensation devices identified through the installed capacity, type (capacitor banks or static VAR compensator) and their locations;
energy storage systems are identified through the installed capacity and their locations.
end-users characterized by type (single-phase/three-phase), the location in the AEDNs (the connection pillars), the connection phase (for single-phase end-users);
energy generation systems installed to the prosumers characterized by the installed capacity.
The RBES uses the data communication between the smart meters installed at all end-users and the data concentrator installed in the MV/LV EDS. These data form the dynamic database of the RBES, together with the outcomes of the steady-state calculations, represented by the values of the voltage from the nodes:
upper and lower allowable limits of the voltages imposed by the quality power standards;
information from the smart metering system associated with the injected/requested powers by the end-users (prosumers/consumers) at the fixed time slots (depending on setting the sampling step of the smart meters), the annual energy production/consumption;
values of the nodal voltages, power flows, and power losses resulted from the steady-state calculations performed with a performance algorithm characterized by fast convergence and reduced calculation time considering the topology of the AEDNs identified through the data recorded in the static database at the request of the inference engine.
The inference engine accesses the data that, through the rule-based motivation, decide whether to modify or not the tap position of OLTC such that all voltages are inside the allowable limits fixed by the DNO. In the RBES, an IF-THEN production rule set represents the domain knowledge, and data are associated with a fact set about the current situation. The data and rules are then compared with the facts in the database. When the conditions of the rule match a fact, the system fires the rule and its active component is executed. A code that has the following syntax,
"IF conditions, THEN actions."
belongs to each rule.
The rule-based reasoning method, integrated into the inference engine and used to analyse the data, is based on the following approach. The knowledge base contains the rules designed to guide the system in performing its task (suitable voltage level according to the power quality performance standard). Thus, the expert system has the goal and the inference engine attempts to find the evidence to prove it. First, the knowledge base is interrogated to find rules that might lead to the desired solution. Such rules must have the goal in their THEN (action) parts. If such a rule is found and the part of the condition associated with IF matches data in the database, then the rule is fired, and the goal is proved.
The information collected during a time slot s by smart meters (active and reactive powers) installed to the end-users (prosumers and consumers) is sent to the data concentrator from the EDS level through the communication system. The data belong to an operation regime of the AEDN where the tap position of the OLTC, identified by the variable α, corresponds to the previous time slot (s-1), with s = 1, …, S, S representing the analysed period.
The RBRS establishes the tap position of the OLTC starting with the time slot s, s = 1, …, S, based on the data obtained from the steady-state calculations performed with a fast algorithm [
42] using the tap position from the time slot (s-1), α
(s-1), and the information from the database (static and dynamic). The next step confirms that the data are available to determine the extreme values (minimum and maximum) of the voltage at the level of LV AEDN.
where:
γ – the index used to identify one of the three phases γ {γa , γb , γc};
NE – the variable referring to the total number of the nodes from the AEDNs;
e – the index associated with a certain node from the AEDN;
A – the upper tap of OLTC;
α – the index corresponding with the tap position in a certain time slot;
S – the total number of the time slots defined in the analysed period;
s – the time slot identified in the analysed period S;
– the voltage on the phase, γ, γ {γa , γb , γc} calculated in each node e, e = 1, …, NE, for the time slot s, s = 1, …, S, and the tap position α associated with the time slot s-1;
, – the extreme values of the voltages from the AEDN (regardless of the phase) determined from the time slot s, and the tap position α associated with the time slot (s-1).
The voltage control in each time slot s refers to an iterative process having the stop criterion associated with the extreme values (minimum and maximum) of the voltage at the level of AEDN, which must be between allowable limits:
If the extreme values V
mins,α(s-1), V
maxs,α(s-1) exceed the allowable limits (V
mina and V
maxa) specified in the power quality performance standard, then the tap position is modified with a step Δα
s(k) in each iteration k of the time slot s based on the following rules [
26,
43]:
where:
ΔV
α represents the voltage changes per tap.
But, the tap position can be modified if the constraints regarding the dead band (DB) of the OLTC are satisfied [
44]:
where: V
r is reference voltage.
When the voltage deviation exceeds DB (having value ΔVα/2), the tap position can be changed. The use of the deadband can avoid the effects of unnecessary tap-changing operations.
Figure 3 presents the flow chart of the voltage control using rule-based reasoning.
The user can ask the expert system how it reaches a particular conclusion through the explanation facilities, which allows one to understand the reasoning behind the decision. The RBES can provide a credible and effective solution based on a clear explanation of its analysis and guidance. The proposed guidance is systematic, evaluating the effects of the voltage control on the operation of the LV AEDN, avoiding conflicts between the rules. Although these components represent the core of the RBES, additional parts could be integrated. One of these is the external interface that allows the RBES to interact with other programs and data files used commonly by the DNOs (smart metering, SCADA, Demand Management System).
The main characteristics of the proposed RBES are efficiency and resilience. Efficiency is the ability to meet the demands of the end-users regarding voltage quality. Regarding the second characteristic, it covers the capacity of the RBES to respond to harmful events associated with sudden voltage variations due to the intermittent regime of the small-scale renewable sources (prosumers).
3. Results
The proposed RBES has been tested considering an aerial LV EDN supplied by an EDS whose MV bus (20 kV) represents the CCP with the network of a Romanian DNO that carries out its distribution service in the respective area.
Figure 4 shows the structure of the test LV EDN.
The EDS contains an MV/LV (20/0.4 kV) distribution transformer, having the following technical features associated with a Tier 2 transformer [
45]:
rated power, Sr = 250 kVA;
load power loss, ΔPl = 2.35 kW;
no-load power loss, ΔPnl = 0.27 kW;
OLTC with 9 taps (tapping range ±10%), where the median tap is 5, voltage step 2.5%, and the number of tap operations without maintenance is 700,000 [
43].
The LV EDNs is an aerial network with four conductors (three phases and a neutral) having detailed features in
Table 1, to which 114 end-users are connected at the three phases and presenting the distribution from
Figure 5.
The total length of the network is 3.52 km having two types of conductors (classical and stranded). The sections with the classical conductor have 3.4 km, representing 96.6% of the total length). The most common cross-section is 50 mm2 (mainly on the trunk of the network, P1 – P88), representing 62.5%, followed by 35 mm2 and 25 mm2 (found on the lateral branch, P4 – P39).
All end-users are integrated into the Smart Metering System, and the data regarding the consumed active and reactive powers are available. The sampling step set for all smart meters to send this information to the data concentrator is 60 minutes.
Localization of the network is in an area where the solar potential is very high, so it is expected that the number of consumers who want to become PV prosumers will increase a lot, considering the situation in Romania. According to the last report of the Romanian Energy Regulatory Authority (RERA) published in 2022 [
46], the prosumers increased more than 6 times in 2021, from 2134 to 13,596. On the other hand, the reports of the RERA regarding the evolution of energy consumption from 2020 – 2022 [
47] highlighted a decrease at the residential consumer level by approximately 10%. This decrease was due to two factors associated with the pandemic crisis and geopolitical (the war in Ukraine and the energy crisis).
In this context, more scenarios have been considered characterized by the following indicators: penetration degree, PD, PD
{0%, 10%, 20%, 30%, 40, and 50%}; consumption evolution, CEC, CEC
{-10%, - 5%, 0%, +5%, +10%}; and energy production of the PV systems from the month which includes the analysed day, EP
PV, EP
PV{
-
,
, +
}, where
and
represent the mean and standard deviation of the energy production (EP) associated with a PV system from the geographical area where the LV EDN is located, having a certain installed capacity for a month from a year (in our case, June). Knowing the values
and
, EP
PV with probability (confidence level) 0.95 belonging to the interval [
-
,
+
] (confidence interval) has been considered. This means that, in almost all cases, the frequency will not go beyond the specified interval. Even in 5% of cases, the errors will be minor [
48].
The study analysed the penetration degrees considering the assumption that the consumers with the highest energy consumption are qualified and selected to become prosumers, maintaining their connection phase.
Table A1 from
Appendix A presents the allocation of the end-users, classified as consumers and prosumers, at each pillar associated with the five penetration degrees, PD
{0%, 10%, 20%, 30%, 40, and 50%}. Considering the energy consumptions uploaded from the SMS, the PV systems have been sized (having the installed capacities of 3 and 5 kWp ) based on the generation profiles from the geographical location of the LV EDN uploaded from the PVGIS tool [
49]. Another assumption refers to prosumers who do not have energy storage systems, representing the current situation in Romania.
Figure 6 and
Figure 7 present the generation profiles of the two PV systems (3 and 5 kWp),
-
(low energy production),
(average energy production) and
+
(high energy production)
, determined for June and used in the analysed scenarios.
The number of the scenarios (SC) obtained from the combinations between the three indicators is N
SC = PD x CEC x EP
PV = 5 x 5 x 3 = 75, see
Table 2, to which is added the base scenario (S0), represented by the current situation where PD = 0, CEC = 0, and EP
PV = 0.
The MV side of the EDS represents in our study the slack node used in the steady-state calculations, but all results will refer only to the low voltage part to highlight the impact of RBES on the AEDN.
Figure 8 presents the aggregation of the active powers at the LV level (0.4 kV) of the EDS for the analysed day from June associated with scenario S0 in the case study. In this scenario, the OLTC operates on tap α
s = 8 regardless of the time slot s, s = 1, …, 24. The high differences between loads of the three phases can be observed, with an unfavourable effect on the energy losses in the LV AEDN due to the pronounce unbalance degree reflected on the additional circulations in the neutral conductor, see
Figure 9.
The highest energy losses are in the conductor from the phase γb (48.4%), followed by neutral (38.5%), phase γc (9.6%), and phase γa (3.4%), where the values have been reported to the total energy losses (77.03 kWh). The energy losses contain only the component associated with the losses in conductors. However, the LV EDNs with the high unbalance degree represents a common feature of the Romanian distribution system, indicating that the DNO should solve the unbalance issue before integrating prosumers that could cause additional issues, as will be presented in the following.
Regarding the voltage quality, all phase voltages at the pillar level have values inside the allowable range [-10%, +10%] according to the European Standard EN 50160 [
50], even if the OLTC has a constant tap position, α = 8.
Figure 10 presents the phase voltage variation in the analysed period, where more values are very close to the lower limit value (0.9).
In the next step, operating the LV EDN without using the RBES in the OLTC-based voltage control in all scenarios presented in
Table 1 has been considered.
Table 3 and
Table 4 present the results associated with the minimum and maximum phase voltages and total energy losses obtained after performing the steady-state calculations, where the tap position of OLTC has been considered constant, α = 8, for all time slices, s = 1, …, S, in all scenarios presented in
Table 2 and identified by the values of PD, EP
PV, and CEC. The following notations have been used for the indicator EP
PV: low energy production - EP
LPV (EP
LPV =
-
), average energy production – EP
APV (EP
APV =
), and high energy production – EP
HPV (EP
HPV =
+
).
The analysis of results presented in
Table 3 highlighted that in 40 scenarios (53.3%) from the total number, the phase voltage exceeded the upper allowable value (1.1 p.u.). All values over 1.1 p.u. are highlighted in the table in bold. These situations have been recorded in the phases γ
a and γ
c where the requested power of the consumers has been small, and the injected power of the prosumers has been high, which led to increases between 0.005 p.u. (scenario S30, with PD = 20%, CEC = 10 %, and EP
HPV) and 0.185 p.u. (scenario with PD = 50%, CEC = - 10 %, and EP
HPV).
Regarding the energy losses, the values are lower for 58 scenarios (77.33% of the total number) than in the base scenario, S0 (ΔW = 77.03 kWh). The higher values, highlighted with bold font in the table, have been recorded for PD = 40%, 50%, EPHPV, and all considered possibilities of CEC, CEC {-10, -5, 0, 5, 10}. Also, the energy losses decrease on the columns top-down (from the smaller to higher CEC) and increase on the rows left to right (from the lower to higher PD and EPPV), aspects usually encountered in the LV EDNs. The minimum energy losses correspond to scenarios S31 – S35 with a PD = 30%, all values of CEC, CEC {-10, -5, 0, 5, 10}, and EPLPV.
A scenarios-based voltage quality matrix can be available to the DNO, indicating possible future values of the maximum phase voltage in the LV EDNs and highlighting worst scenarios (red colour and larger font size) such that the best corrective measures are considered, see
Figure 11. The matrix presents rows associated with the CEC possibilities that go top-down (from small to high) and columns with various alternatives for the EP
PV and PG that follow one another from left to right.
It is clear that if the RBES-based voltage control, which uses the advantages of the OLTC, is not used, the DNO can have issues with the integration in the LV EDN of an increasing number of prosumers correlated with changes in energy consumption that may occur at the level of consumers.
Thus, the results have been obtained by applying the proposed RBES-based voltage control for the scenarios with the voltage issues identified in the previous step.
Table 5 and
Table 6 present the data associated with these scenarios in bold font. For the scenarios without voltage issues, the maximum voltage corresponds to the steady state without applying the RBES-based voltage control.
The voltage issues have been removed for 30 of 40 scenarios where the maximum values of the phase voltage exceeded the upper allowable limit.
The remaining scenarios with voltage issues, (S56 – S60, and S71 – S75), identified with red colour and bold font in
Table 5 and the scenarios-based voltage quality matrix represented in
Figure 12, are associated with PD
{40%, 50%}, EP
HPV, and CEC
{-10%, -5%, 0%, 5%, 10%}, even if the maximum value of the phase voltage has been reduced with the values between 0.12 p.u (scenario S56, PD = 40%, EP
HPV, and CEC = -10%), which means 9.5%, and 0.15 p.u. (scenario S75, PD = 50%, EP
HPV, and CEC = +10%), which means 11.6%. But, at least 95% of the time slots, the voltages have been inside the range [-10%, +10%], according to the European Power Quality Standard.
The energy losses in the conductors for the scenarios (S26 – S30), where PD = 20%, EPHPV, and CEC {-10%, -5%, 0%, 5%, 10%}, and (S36 – S40), where PD = 30%, EPAPV, and CEC {-10%, -5%, 0%, 5%, 10%}, are slightly lower between 0.21% (S26 and S36) and 5.16% (S30). For all others scenarios (S41 – S45 and S51 – S75) the values are higher, especially for S56 – S60, where PD = 40%, EPHPV, and CEC {-10%, -5%, 0%, 5%, 10%}, and S71 – S75, where PD = 50%, EPHPV, and CEC {-10%, -5%, 0%, 5%, 10%}. Also, the last scenarios have voltage issues (as previously emphasized) corresponding to the largest energy amount injected by the prosumers in the network.
Regarding these scenarios, another voltage quality index is used to quantify the unallowable voltage variations, see
Table 7. This index calculates with relation (10) shows the percentage of the time slots in which the phase voltage deviations exceed the allowable limits.
where the signification of all variables has been indicated in
Section 2.
The values of UVD from
Table 7 indicated that the phase voltages in the nodes (at the pillar level) of the LV EDN for all 10 scenarios are outside the range [-10%, +10], in a percentage between 1.73% and 4.98%. Higher percentages, between 4.49% and 4.98 %, have been recorded for scenarios S71 – S75. In these conditions, the DNOs should be very careful and take additional measures to improve the voltage level in the LV EDN, and one of them can be the phase load balancing [
51], taking into account the higher unbalance degree emphasized in the base scenario, S0.
The obtained results have been compared with an efficient method, which proved its effectiveness in voltage control, having the same assumptions as in the proposed RBES. The control voltage has been treated as a multi-objective problem where the optimal tap positions of the OLTC in each time slot are determined to minimize the energy losses and voltage deviations in the presence of technical constraints associated with the operating of the LV EDN [
6].
Table 8 presents the errors associated with the energy losses between the two methods calculated with the relation:
where: ΔW
MM represents the energy losses calculated with the multiobjective method (MM) and ΔW
RBED corresponds to the energy losses determined with the proposed RBES.
The analysis of the data highlighted that the energy losses are slightly smaller in the case of RBES compared with the MM method, with differences between 0.85 % (PD = 50%, EPAPV, and CEC = 10%) and 3.54% (PD = 20%, EP
APV, and CEC = - 10%). The similar values of the maximum phase voltage have been obtained in 47 scenarios (62.7%) highlighted through null values of the errors, see
Table 9. However, the maximum values are slightly higher in the other scenarios (28) for the RBES compared with the MM method, between 0.08% (PD = 10%, EP
LPV, and CEC = -10%) and 2.62% (PD = 40%, EP
LPV, and CEC = -10%). Also, the voltage issues have not been solved fully for scenarios S56 – S60 and S71 – S75, but at least 95% of the time slots, the voltages have been inside the range [-10%, +10%], according to the European Power Quality Standard, and for the rest of the time slots up to 100% have been very close to the limits of the range.
The highest differences have been identified at the level of the optimization variables (the tap positions). A comparison between methods has been made only for the scenarios with voltage issues highlighted with bold font in the tables. The total number of tap position changes is higher in the MM method than in the RBES, which makes RB more efficient, see
Table 10.
Table A2 and A3 from
Appendix A presents the tap position changes for the two methods.
4. Discussions and conclusions
The voltage quality, represented by exceeding the admissible limits indicated in the performance standards, has been identified by the DNOs as one of the main factors that can decrease the hosting capacity to accommodate the growing number of PV prosumers. The reverse power flows from the LV EDN toward the EDS ensure the connection between the MV and LVEDNs and represent the reason for various voltage issues, leading to uncertainties on the voltage level of the nodes. Thus, new methodologies should be developed to solve the voltage issues caused by PV prosumers based on the devices integrated into the EDN.
One of the most efficient devices to ensure the resilience of voltage control, which demonstrated its performance at the HV level, is represented by the OLTC, which equips the MV/LV distribution transformers. One of the most challenging issues in the operation of the OLTC in the LV EDNs is the determination of the optimal tap position, which leads to a fit 95% of the time between the admissible limits of the phase voltage in all nodes following the performance standards, in conditions when the reverse power flows can occur.
In these conditions, an efficient expert system, including rule-based reasoning (RBES), has been developed having as the advantages: the "fast-scanning" of the input data, identification of voltage issues that come up, determination of a solution associated with the tap position of an OLTC that does not violate the voltage constraints in the PV-rich network based on the deviations between the reference voltage and the voltages recorded in the nodes in each time slot recognizing the excesses of the allowable limits, regardless of the power flow's direction. These advantages offer RBES efficiency and resilience. Efficiency is associated with their ability to meet the demands of the end-users regarding voltage quality, and resilience characterizes by the response to harmful events represented by sudden voltage variations due to the intermittent regime of the small-scale renewable sources (prosumers).
Testing the RBES has been done considering an aerial LV EDN supplied by an EDS whose MV bus (20 kV) represents the CCP with the network of a Romanian DNO that carries out its distribution service in the respective area. More scenarios (75) have been considered in the case study, characterized by the combinations between the penetration degree, PD, PD {0%, 10%, 20%, 30%, 40, and 50%}; consumption evolution, CEC, CEC {-10%, - 5%, 0%, +5%, +10%}; and energy production of the PV systems from the month which includes the analyzed day, low energy production EPLPV – (EPLPV = - ), average energy production – EPAPV (EPAPV = ), and high energy production – EPHPV (EPHPV = + ), where and represent the mean and standard deviation of the energy production (EP) associated with a PV system from the geographical area of the LV EDN.
The success rate of the RBES has been 86.7% (65 out of 75 scenarios didn't have the voltage issues anymore. For the remaining scenarios (S56 – S60, and S71 – S75) associated with PD {40%, 50%}, EPHPV, and CEC {-10%, -5%, 0%, 5%, 10%}, the voltage has been mitigated being close to the upper allowable limit, but at least 95% of the time slots has been inside the range [-10%, +10%], according to the European Power Quality Standard.
The comparison with an efficient method demonstrated the efficiency of the RBES, quantified through smaller energy losses and the total number of tap position changes. Even under these conditions, the implementation of RBES in the real application integrated into the LV EDNs depends on the speed and sampling step of the data transmission from the smart meters installed to the end-users and the performance of the processing module from the data concentrator at the EDS level.
The authors work now on an improved variant of the RBES, which includes a opanimization process associated with phase load balancing to remove the voltage issues for higher penetration degrees, as observed in the case study.
Figure 1.
The evolution of the voltage in the LV EDNs without and with PV prosumers integrated.
Figure 1.
The evolution of the voltage in the LV EDNs without and with PV prosumers integrated.
Figure 3.
The flow chart of the voltage control using the rule-based reasoning.
Figure 3.
The flow chart of the voltage control using the rule-based reasoning.
Figure 4.
The test 88-bus LV EDN.
Figure 4.
The test 88-bus LV EDN.
Figure 5.
The allocation of the end-users at the phases of the test 88-bus LV EDN.
Figure 5.
The allocation of the end-users at the phases of the test 88-bus LV EDN.
Figure 6.
The generation profiles of the PV system with 3 kWp installed powers with the probability that EC of 0.95 (low, mean, and high energy production).
Figure 6.
The generation profiles of the PV system with 3 kWp installed powers with the probability that EC of 0.95 (low, mean, and high energy production).
Figure 7.
The generation profiles of the PV system with 5 kWp installed powers with the probability that EC of 0.95 ((low, mean, and high energy production).
Figure 7.
The generation profiles of the PV system with 5 kWp installed powers with the probability that EC of 0.95 ((low, mean, and high energy production).
Figure 8.
The aggregation of the active powers at the LV level (0.4 kV) of the EDS for the analysed day from June associated with scenario S0.
Figure 8.
The aggregation of the active powers at the LV level (0.4 kV) of the EDS for the analysed day from June associated with scenario S0.
Figure 9.
The energy losses in the conductors of the LV AEDN in the analysed period (24 hours).
Figure 9.
The energy losses in the conductors of the LV AEDN in the analysed period (24 hours).
Figure 10.
The phase voltages at the level of the end pillar (P88).
Figure 10.
The phase voltages at the level of the end pillar (P88).
Figure 11.
The scenarios-based voltage quality matrix indicating possible future values of the maximum phase voltage recorded for each scenario associated with the LV EDN.
Figure 11.
The scenarios-based voltage quality matrix indicating possible future values of the maximum phase voltage recorded for each scenario associated with the LV EDN.
Figure 12.
The scenarios-based voltage quality matrix indicating possible future values of the maximum phase voltage recorded for each scenario identified associated with the LV EDN, with applying RBES.
Figure 12.
The scenarios-based voltage quality matrix indicating possible future values of the maximum phase voltage recorded for each scenario identified associated with the LV EDN, with applying RBES.
Table 1.
The technical features of the test 88-bus LV EDN.
Table 1.
The technical features of the test 88-bus LV EDN.
Type of section |
Conductor |
Type of conductor |
Length [km] |
Cross-section of phase conductor |
Number of phases |
Cross-section of neutral conductor |
1 |
50 |
3 |
50 |
C* |
2.08 |
2 |
50 |
3 |
50 |
S** |
0.12 |
3 |
35 |
3 |
35 |
C* |
0.68 |
4 |
35 |
1 |
35 |
C* |
0.28 |
5 |
25 |
1 |
25 |
C* |
0.28 |
6 |
25 |
1 |
16 |
C* |
0.08 |
* C – classical conductor (aluminium conductor steel-reinforced cable) **S - Stranded conductor |
Table 2.
The analyzed scenarios (SA) with the features of the three indicators.
Table 2.
The analyzed scenarios (SA) with the features of the three indicators.
SC |
PD [%] |
EPPV [kWh] |
CEC [%] |
SC |
PD [%] |
EPPV [kWh] |
CEC [%] |
SC |
PD [%] |
EPPV [kWh] |
CEC [%] |
S1 |
10 |
-
|
-10% |
S26 |
10 |
|
-10% |
S51 |
10 |
+
|
-10% |
S2 |
10 |
-
|
-5% |
S27 |
10 |
|
-5% |
S52 |
10 |
+
|
-5% |
S3 |
10 |
-
|
0% |
S28 |
10 |
|
0% |
S53 |
10 |
+
|
0% |
S4 |
10 |
-
|
+5% |
S29 |
10 |
|
+5% |
S54 |
10 |
+
|
+5% |
S5 |
10 |
-
|
+10% |
S30 |
10 |
|
+10% |
S55 |
10 |
+
|
+10% |
S6 |
20 |
-
|
-10% |
S31 |
20 |
|
-10% |
S56 |
20 |
+
|
-10% |
S7 |
20 |
-
|
-5% |
S32 |
20 |
|
-5% |
S57 |
20 |
+
|
-5% |
S8 |
20 |
-
|
0% |
S33 |
20 |
|
0% |
S58 |
20 |
+
|
0% |
S9 |
20 |
-
|
+5% |
S34 |
20 |
|
+5% |
S59 |
20 |
+
|
+5% |
S10 |
20 |
-
|
+10% |
S35 |
20 |
|
+10% |
S60 |
20 |
+
|
+10% |
S11 |
30 |
-
|
-10% |
S36 |
30 |
|
-10% |
S61 |
30 |
+
|
-10% |
S12 |
30 |
-
|
-5% |
S37 |
30 |
|
-5% |
S62 |
30 |
+
|
-5% |
S13 |
30 |
-
|
0% |
S38 |
30 |
|
0% |
S63 |
30 |
+
|
0% |
S14 |
30 |
-
|
+5% |
S39 |
30 |
|
+5% |
S64 |
30 |
+
|
+5% |
S15 |
30 |
-
|
+10% |
S40 |
30 |
|
+10% |
S65 |
30 |
+
|
+10% |
S16 |
40 |
-
|
-10% |
S41 |
40 |
|
-10% |
S66 |
40 |
+
|
-10% |
S17 |
40 |
-
|
-5% |
S42 |
40 |
|
-5% |
S67 |
40 |
+
|
-5% |
S18 |
40 |
-
|
0% |
S43 |
40 |
|
0% |
S68 |
40 |
+
|
0% |
S19 |
40 |
-
|
+5% |
S44 |
40 |
|
+5% |
S69 |
40 |
+
|
+5% |
S20 |
40 |
-
|
+10% |
S45 |
40 |
|
+10% |
S70 |
40 |
+
|
+10% |
S21 |
50 |
-
|
-10% |
S46 |
50 |
|
-10% |
S71 |
50 |
+
|
-10% |
S22 |
50 |
-
|
-5% |
S47 |
50 |
|
-5% |
S72 |
50 |
+
|
-5% |
S23 |
50 |
-
|
0% |
S48 |
50 |
|
0% |
S73 |
50 |
+
|
0% |
S24 |
50 |
-
|
+5% |
S49 |
50 |
|
+5% |
S74 |
50 |
+
|
+5% |
S25 |
50 |
-
|
+10% |
S50 |
50 |
|
+10% |
S75 |
50 |
+
|
+10% |
Table 3.
The maximum value of the phase voltage obtained after performing the steady-state calculations in the analysed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) without applying RBES.
Table 3.
The maximum value of the phase voltage obtained after performing the steady-state calculations in the analysed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) without applying RBES.
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
1.053 |
1.053 |
1.053 |
1.053 |
1.074 |
1.130 |
1.059 |
1.127 |
1.201 |
1.081 |
1.175 |
1.263 |
1.128 |
1.209 |
1.285 |
-5 |
1.053 |
1.053 |
1.053 |
1.053 |
1.065 |
1.125 |
1.057 |
1.119 |
1.196 |
1.075 |
1.167 |
1.259 |
1.125 |
1.207 |
1.283 |
0 |
1.053 |
1.053 |
1.053 |
1.053 |
1.064 |
1.118 |
1.054 |
1.114 |
1.189 |
1.071 |
1.162 |
1.252 |
1.123 |
1.205 |
1.281 |
5 |
1.053 |
1.053 |
1.053 |
1.053 |
1.063 |
1.110 |
1.053 |
1.109 |
1.182 |
1.068 |
1.157 |
1.245 |
1.121 |
1.201 |
1.279 |
10 |
1.053 |
1.053 |
1.053 |
1.053 |
1.062 |
1.105 |
1.053 |
1.103 |
1.177 |
1.066 |
1.152 |
1.241 |
1.119 |
1.201 |
1.278 |
Table 4.
The total energy losses in the conductors calculated in the analysed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) without applying RBES.
Table 4.
The total energy losses in the conductors calculated in the analysed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) without applying RBES.
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
39.4 |
42.5 |
48.0 |
41.8 |
42.8 |
48.2 |
39.4 |
47.6 |
70.8 |
40.0 |
62.0 |
107.5 |
46.1 |
85.4 |
157.1 |
-5 |
44.4 |
48.5 |
54.3 |
46.6 |
48.3 |
51.9 |
44.2 |
51.3 |
73.0 |
44.1 |
64.7 |
108.5 |
49.9 |
87.6 |
157.4 |
0 |
50.0 |
54.9 |
61.2 |
51.8 |
54.4 |
56.2 |
49.5 |
55.2 |
75.8 |
48.7 |
67.6 |
110.2 |
54.1 |
90.0 |
158.2 |
5 |
56.1 |
61.3 |
68.5 |
57.1 |
60.9 |
60.9 |
55.1 |
59.4 |
79.0 |
53.6 |
70.9 |
112.1 |
58.7 |
92.8 |
159.5 |
10 |
62.2 |
68.3 |
76.2 |
62.9 |
65.6 |
67.8 |
61.5 |
64.0 |
82.3 |
59.3 |
74.5 |
114.3 |
64.0 |
95.9 |
161.0 |
Table 5.
The maximum value of the phase voltage obtained after performing the steady-state calculations in the analyzed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) with applying RBES.
Table 5.
The maximum value of the phase voltage obtained after performing the steady-state calculations in the analyzed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) with applying RBES.
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
1.053 |
1.053 |
1.053 |
1.053 |
1.074 |
1.090 |
1.059 |
1.089 |
1.098 |
1.081 |
1.087 |
1.143 |
1.097 |
1.095 |
1.137 |
-5 |
1.053 |
1.053 |
1.053 |
1.053 |
1.065 |
1.100 |
1.057 |
1.100 |
1.100 |
1.075 |
1.099 |
1.138 |
1.100 |
1.097 |
1.135 |
0 |
1.053 |
1.053 |
1.053 |
1.053 |
1.064 |
1.096 |
1.054 |
1.095 |
1.098 |
1.071 |
1.098 |
1.131 |
1.098 |
1.099 |
1.133 |
5 |
1.053 |
1.053 |
1.053 |
1.053 |
1.063 |
1.091 |
1.053 |
1.089 |
1.098 |
1.068 |
1.093 |
1.123 |
1.098 |
1.097 |
1.131 |
10 |
1.053 |
1.053 |
1.053 |
1.053 |
1.062 |
1.091 |
1.053 |
1.091 |
1.098 |
1.066 |
1.091 |
1.118 |
1.096 |
1.095 |
1.129 |
Table 6.
The total energy losses in the conductors calculated in the analyzed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) by applying RBES.
Table 6.
The total energy losses in the conductors calculated in the analyzed scenarios characterized by the features of the three indicators (PD, EPV, and CEC) by applying RBES.
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
39.4 |
42.5 |
48.0 |
41.8 |
42.8 |
48.1 |
39.4 |
47.5 |
77.4 |
40.0 |
65.8 |
127.8 |
46.6 |
95.5 |
191.3 |
-5 |
44.4 |
48.5 |
54.3 |
46.6 |
48.3 |
51.7 |
44.2 |
51.1 |
78.6 |
44.1 |
67.8 |
128.0 |
49.9 |
97.1 |
190.5 |
0 |
50.0 |
54.9 |
61.2 |
51.8 |
54.4 |
55.6 |
49.5 |
54.6 |
80.3 |
48.7 |
69.1 |
128.5 |
53.7 |
97.9 |
190.0 |
5 |
56.1 |
61.3 |
68.5 |
57.1 |
60.9 |
60.2 |
55.1 |
58.7 |
82.6 |
53.6 |
72.1 |
129.9 |
58.1 |
100.2 |
190.6 |
10 |
62.2 |
68.3 |
76.2 |
62.9 |
65.6 |
64.3 |
61.5 |
62.7 |
84.9 |
59.3 |
75.1 |
130.0 |
62.8 |
102.5 |
190.5 |
Table 7.
The values of UVD, in [%], calculated for the scenarios S56 - S60 and S71 - S75. (EPHPV = + ).
Table 7.
The values of UVD, in [%], calculated for the scenarios S56 - S60 and S71 - S75. (EPHPV = + ).
PD [%] |
CEC [%] |
-10 |
-5 |
0 |
5 |
10 |
40 |
2.86 / S57 |
2.48 / S56 |
2.11 / S58 |
1.87 / S59 |
1.73 / S60 |
50 |
4.98 / S71 |
4.91 / S72 |
4.71 / S73 |
4.60 / S74 |
4.49 / S75 |
Table 8.
The errors between the energy losses calculated with the MM method and RBES, in [%].
Table 8.
The errors between the energy losses calculated with the MM method and RBES, in [%].
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
2.50 |
2.85 |
2.96 |
2.84 |
3.54 |
2.87 |
3.19 |
3.32 |
1.60 |
3.46 |
2.05 |
0.00 |
3.04 |
1.04 |
0.00 |
-5 |
2.18 |
2.10 |
2.10 |
2.08 |
2.78 |
2.99 |
2.29 |
3.60 |
1.56 |
3.02 |
2.28 |
0.00 |
2.90 |
1.02 |
0.00 |
0 |
1.89 |
1.77 |
1.64 |
1.75 |
2.31 |
2.68 |
1.91 |
2.60 |
1.61 |
2.14 |
2.05 |
0.00 |
2.18 |
1.16 |
0.00 |
5 |
1.50 |
1.78 |
1.68 |
1.77 |
2.19 |
2.60 |
1.84 |
2.50 |
1.41 |
2.10 |
1.77 |
0.00 |
2.31 |
0.94 |
0.00 |
10 |
1.34 |
1.61 |
1.47 |
1.79 |
1.84 |
2.32 |
1.60 |
2.21 |
1.38 |
1.80 |
1.50 |
0.00 |
2.08 |
0.85 |
0.00 |
Table 9.
The errors between maximum values of the phase voltage calculated with the MM method and RBES, in [%].
Table 9.
The errors between maximum values of the phase voltage calculated with the MM method and RBES, in [%].
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
0.08 |
0.08 |
0.08 |
0.08 |
1.98 |
0.53 |
0.62 |
0.91 |
0.35 |
2.62 |
0.00 |
0.00 |
1.35 |
0.00 |
0.00 |
-5 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
1.83 |
0.00 |
2.27 |
0.00 |
0.85 |
1.68 |
0.00 |
1.85 |
0.00 |
0.00 |
0 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
1.68 |
0.00 |
1.57 |
0.00 |
0.17 |
0.17 |
0.00 |
1.87 |
0.00 |
0.00 |
5 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
1.23 |
0.00 |
1.11 |
0.00 |
0.24 |
0.24 |
0.00 |
1.89 |
0.00 |
0.00 |
10 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.44 |
0.00 |
0.00 |
0.00 |
0.45 |
0.00 |
0.00 |
Table 10.
The additional tap position changes of the OLTC (MM vs. RBES).
Table 10.
The additional tap position changes of the OLTC (MM vs. RBES).
CEC [%] |
PD [%] |
10 |
20 |
30 |
40 |
50 |
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
EPLPV
|
EPAPV
|
EPHPV
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 |
0 |
0 |
0 |
0 |
0 |
4 |
0 |
4 |
4 |
0 |
4 |
0 |
6 |
1 |
0 |
-5 |
0 |
0 |
0 |
0 |
0 |
4 |
0 |
4 |
2 |
0 |
2 |
0 |
4 |
1 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
4 |
0 |
4 |
2 |
0 |
4 |
0 |
0 |
2 |
0 |
5 |
0 |
0 |
0 |
0 |
0 |
4 |
0 |
4 |
2 |
0 |
4 |
0 |
2 |
2 |
0 |
10 |
0 |
0 |
0 |
0 |
0 |
4 |
0 |
4 |
2 |
0 |
2 |
0 |
2 |
2 |
0 |