3.1. Research on the model of train passing through the neutral zone
In the tested Beijing–Zhangjiakou railway line, the AT power supply mode is adopted, and an autotransformer is installed every 10–15km. One terminal is connected to the contact line, the other terminal is connected to the positive feeder, and the neutral point is directly connected to the rail. As shown in
Figure 5, the AT power supply mode is equipped with a protection wire (PW), which is directly connected in parallel with the rail (R); a connector of protective wire (CPW) is added to connect the rail and the midpoint of the autotransformer with the protection wire. In order to reduce the impedance of the traction power system, increase the voltage at the end of the feeding section, and reduce the power loss, the downstream contact lines, positive feeders, and steel rails of the double–track traction line are connected in parallel at each AT.
Table 4.
Equivalent circuit distributed capacitance calculation results.
Table 4.
Equivalent circuit distributed capacitance calculation results.
c |
T1 |
R1 |
P1 |
F1 |
T2 |
R2 |
P2 |
F2 |
T1 |
13.12 |
–0.83 |
–1.74 |
–2.04 |
–2.00 |
–0.41 |
–0.36 |
–0.56 |
R1 |
–0.83 |
20.12 |
–0.63 |
–0.23 |
–0.41 |
–0.44 |
–0.12 |
–0.09 |
P1 |
–1.74 |
–0.63 |
8.42 |
–1.12 |
–0.36 |
–0.12 |
–0.08 |
–0.11 |
F1 |
–2.04 |
–0.23 |
–1.12 |
8.28 |
–0.56 |
–0.09 |
–0.11 |
–0.26 |
T2 |
–2.00 |
–0.41 |
–0.36 |
–0.56 |
13.12 |
–0.83 |
–1.74 |
–2.04 |
R2 |
–0.41 |
–0.44 |
–0.12 |
–0.09 |
–0.83 |
20.12 |
–0.63 |
–0.23 |
P2 |
–0.36 |
–0.12 |
–0.08 |
–0.11 |
–1.74 |
–0.63 |
8.42 |
–1.12 |
F2 |
–0.56 |
–0.09 |
–0.11 |
–0.26 |
–2.04 |
–0.23 |
–1.12 |
8.28 |
The electrical parameters of the voltage transformer are shown in
Table 5
Table 5.
Voltage transformer inductance parameters.
Table 5.
Voltage transformer inductance parameters.
Serial Number |
JDZXW5–25J |
JDZXW5A –25J |
JDZXW7–25D |
EMU Type |
CRH3X |
CRH5X |
CR400XF |
Primary DC Resistance 20℃ |
43160Ω |
46488Ω |
43160Ω |
Primary inductance |
11000H–12000H |
11000–12000H |
11000H–12000H |
In the entire EMU, only the pantograph and the roof voltage transformer are connected to the contact line and the articulated electrical split. This main circuit can be equivalent to a high–level circuit composed of resistance, inductance and capacitance. The equivalent circuit is shown in
Figure 6.
In
Figure 6, Ua and Ub are traction power supplies; RS and LS are the resistance and inductance of the traction transformer converted according to the Thevenin circuit equivalent; R1 and L1 are the equivalent resistance and reactance of the contact line feeding section; C1 is the feeding section ground capacitance; C2 is the neutral zone–to–ground capacitance; C12 is the coupling capacitance between the neutral zone and the power supply zone; PT is the roof voltage transformer; Cm is the EMU pantograph–to–ground capacitance; K1 and K2 are equivalent switch. The initial state is the off state, which is used to simulate the circuit conversion process of the over–phase division of the EMU.
When the EMU enters the neutral zone, the equivalent switch K
2 remains open, and the equivalent switch K
1 quickly changes from the open state to the closed state. The neutral zone voltage in this transient process can be determined by the differential equation. Since the core inductances L
m and R
m of the roof voltage transformer are relatively large, and C
1 and C
m are relatively small compared to C
2, the neutral zone and the power supply zone coupling capacitor C
12 are short–circuited after the switch K
1 is closed, so in the differential equation expression, the influence of the parameters L
m, R
m, C
1, C
m, and C
12 can be ignored. If
L=
Ls+
L1,
R=
Rs+
R1,
C=
C2 according to the equivalent circuit of the EMU after the equivalent switching action, the loop equation can be listed:
Among them us is the power supply voltage, the inductor voltage uL=Ldi/dt, the resistance voltage uR=R·i, and the loop current i=CduC/dt. Substituting them into equation (1), the differential equation can be obtained:
Since the impedance of the contact line in the neutral zone is very small, the voltage drop of the contact line impedance in the neutral zone can be ignored. Then the voltage uc at both ends of the neutral zone–to–ground capacitance C2 in the equation (2) is the voltage of the neutral zone on the joint–type electrical split.
Equation (2) is a second–order linear non–homogeneous differential equation with constant coefficients, and its full response can be decomposed into zero input response and zero state response.
The induced voltage of the neutral zone–to–ground capacitance C2 on the electric neutral zone, after the switch K1 is closed, the capacitance C2 discharges to the R–L circuit. The differential equation is:
The zero input expression of the effective circuit is:
Due to the different circuit parameters, the characteristic root may have three different situations. The neutral zone–to–ground voltage in these three situations will be discussed:
1) When
α=
ω0, that is
,
p1 and
p2 are two unequal negative real numbers.
This situation is called aperiodic discharge or non–oscillating discharge process.
2) When
α=
ω0, that is
R<2(
L/
C)
0.5,
p1 and
p2 are equal, then the equivalent circuit has only one frequency, and the neutral voltage to ground is:
It can be seen from equation (6) that there is no oscillating change, and it has a non–oscillating nature, but this is the dividing line between an oscillating circuit and a non–oscillating circuit, so the situation when R<2(L/C)0.5 is called a critical non–oscillating process.
3) When
α <
ω0, that is
R<2(
L/
C)
0.5,
p1 and
p2 are a pair of conjugate complex roots, and the neutral voltage to ground is:
This is an oscillating discharge situation. During the whole process, the waveform will periodically change direction, and the energy storage element will also periodically exchange energy.
When
us=
Umsin(ω
t+
Φ) in formula (2), where
is the angular frequency of the power supply and
Φ is the initial phase angle of the power supply voltage. At this time equation (2) becomes:
1) If it is a non–oscillating circuit, the neutral voltage to ground can be expressed as:
Substituting formula (5) into the formula, the expression of
Uc and
i is:
2) If the circuit is in a critical state, in the same initial state, the same as above can be obtained:
3) If it is an oscillating circuit, at this time
and
are a pair of conjugate complex numbers,
p1=–
α+
jωd,
p2=–
α–
jωd, which can be obtained under the same initial state:
When the EMU enters the neutral zone and low–frequency oscillation occurs, the equivalent circuit is obviously oscillating. According to the principle of circuit superposition, add equations (7) and (6) with equations (12) and (11) respectively, and then we can get the mathematical expression of electric current when the EMU enters the electrical neutral zone.
Combining equation (13) at the moment when the EMU enters the articulated electrical neutral zone, the magnitude of the neutral zone's ground voltage is related to the phase angle of the contact line power supply of the traction substation. The neutral zone structure affects the ground capacitance parameter C, it will also determine the voltage oscillation process in the neutral zone. Since the time when the pantograph enters the neutral zone is random, the instantaneous phase angle of the system power supply voltage is different each time the EMU enters the neutral zone. Therefore, when the EMU enters the electrical neutral zone at different times, different electromagnetic transient processes will be generated, resulting in different excitation levels for the roof voltage transformer. The oscillation angular frequency of the circuit
ω0 is higher than the oscillation frequency of the free component
ωd. The oscillation frequency of the free component
ωd decays exponentially. The speed of the decay depends on the attenuation coefficient
α=R/2L. Obviously, the larger the value
α, the faster the amplitude decays, and the shorter time it takes to decay to zero. Taking into account the contact line impedance
The resistance part is 0.05Ω/km, and the resistance value is about 0.01Ω when the length of the neutral zone is 200m.
Comparing the inductance and resistance parameters of the oscillating system, it can be seen that α=0.001/10000, the damping in the oscillation process is extremely small, and there is almost no attenuation process.
3.2. Oscillation process and overvoltage characteristics
According to the power supply line percenters and the operation status of the train, a source, power supply line and train system model was established, shown in
Figure 7. By changing the on–off state of the time–controlled breaker and the position of the PT in the model, the pantograph–net contact state of the over–phase division of the EMU is simulated. The control breaker is in the open state, and switch quickly to the closed state when entering, and the time control switch controls the closing time and then opens.
In order to explore the influence of the power phase angle on the occurrence of low–frequency oscillation at the moment of separation of the pantograph and the line, the fixed time–controlled switch is adopted to control the closing and opening time. The power phase angle is changed, the occurrence of low–frequency oscillation in the neutral zone is observed, and the power phase angle range is recorded. The maximum voltage amplitude in the neutral zone is corresponding to different phase angles. Under different phase angle conditions, the maximum amplitude of the voltage of the EMU through the neutral zone is shown in
Table 6.
When the phase angle of the power supply is at 60°~90° and 240°~270°, it has a large amplitude. The phenomenon of low frequency oscillation in the neutral zone is most obvious in these phase angle ranges under the simulation conditions. Under the condition of the same power phase angle, the typical waveform of the low–frequency oscillation of the EMU through the electrical neutral zone is shown in
Figure 8.
The frequency spectrum of the low–frequency oscillation line voltage in the neutral zone is analyzed, taking 50Hz as the fundamental frequency. When the low–frequency oscillation phenomenon occurs, the contact line voltage in the neutral zone is mainly 1/3 power frequency (16.7Hz) harmonics.
Figure 9 shows the spectrum analysis graph of the simulation waveform of abnormal line voltage in the neutral zone area.
In the simulation, the low–frequency oscillation voltage waveform is a periodic oscillation waveform, and there is no non–periodic oscillation phenomenon. The occurrence of abnormal grid voltage is mainly determined by the excitation factor (p=ωE) and damping factor (q=1/RC) in the oscillation loop. When the excitation factor is a fixed value, increasing the capacitance or resistance value can reduce the damping factor, which may cause malfunction in the oscillation circuit. The method of increasing the coupling capacitance between the feeding section and the neutral zone is adopted to simulate the abnormal grid voltage phenomenon of the oscillation circuit, as shown in
Figure 10.
The above simulation results show that:
1) The voltage in the neutral zone when the EMU entering the neutral zone is related to the phase angle at the moment when the pantograph separated with the line. If the phase angle when the pantograph separated with the line is between 60°~90° and 240°~270°, the voltage in the neutral zone is large, the maximum amplitude can reach 69.75kV, and low–frequency oscillation will occur in the neutral zone of the electrical neutral zone. The analysis shows that the process of EMU entering the neutral zone has low–frequency oscillation characteristics in the circuit of capacitor voltage and inductance current. Because the phase angle at the time of the separation of the pantograph and the line has randomness, the oscillation process is also random. Therefore, it is verified that within a certain range of power phase angle, the neutral zone will produce a higher overvoltage. The over voltage will stimulate the roof voltage transformer to produce low–frequency oscillation, indicating that the occurrence of low–frequency oscillation is related to power source phase angle when the EMU enters the neutral zone.
2) According to spectrum analysis, when low–frequency oscillation occurs, the voltage of the contact line in the neutral zone is mainly 1/3 power frequency (16.7 Hz) harmonics. This is the same as the frequency characteristics of the measured case of low–frequency oscillation when EMU passes the neutral zone. This match verifies the accuracy of the simulation model.
3) The simulation waveform of the low–frequency oscillation voltage in the neutral zone of the EMU is a periodic oscillation waveform, and there is no non–periodic oscillation. If the length of the feeding section is appropriately increased or the coupling capacitance in the neutral zone is changed, the low–frequency oscillation line voltage in the neutral zone can be slightly suppressed.
3.3. Methods of Suppressing Oscillation Process
As shown in
Figure 10, R1 and L1 are the equivalent impedance of the contact line power supply, C1 is the equivalent capacitance of the traction power system, R2 and C2 represent the resistance and capacitance in the protection device, respectively.
Figure 11(a) only considers the case of parallel resistance. Analysis of this second–order circuit shows that the increase in parallel resistance reduces the damping of the system, and the overvoltage value decreases.
Figure 11(b) only considers the case of parallel capacitors. The same analysis of the second–order circuit shows that the parallel capacitors increase the damping of the system and reduce the overvoltage value. The following equation mainly analyzes the situation in
Figure 11(c). After the switch S is closed, the differential equation about the capacitor voltage uc1 can be listed:
Using Laplace transform, we can obtain:
MATLAB is used to analyze the unit step response of the transfer function, and the results are shown in
Figure 12 to
Figure 13.
According to the low frequency oscillation excitation characteristic test of the voltage transformer, the equivalent circuit of the neutral zone after installing RC protection device is shown in
Figure 13. The transient process of the EMU passing the neutral zone is simulated with PSCAD/EMTDC software, and the simulation model is shown in
Figure 14.
Under the same simulation conditions as the original low–frequency oscillation, an RC device was installed in the neutral zone, and the voltage waveform of the contact line in the neutral zone is shown in
Figure 15.
It can be seen from the simulation waveform that after the suppression device is installed, when the EMU enters the electrical neutral zone and the time–controlled switch in the simulation model is closed, the absolute value of the voltage peak drops to below 20 kV. Compared with the situation without the suppression device, the absolute value of the peak voltage has been reduced by nearly 30%, and the low frequency oscillation has been effectively suppressed. In the simulation, the equivalent circuit of the RC protection device connected in parallel to the roof voltage transformer or the neutral zone of the electric neutral zone is the same, and the suppression effect on the low frequency oscillation is also the same.