1. Introduction
Poor indoor air quality results in various building-related illnesses that negatively impact human health [
1,
2,
3]. Extremely high concentrations of CO
2 (>20,000 ppm) have the potential to be fatal [
4,
5]. In typical indoor environments in non-industrial buildings (<5000 ppm), elevated CO
2 levels impair lung gas exchange function [
6], leading to worker fatigue and drowsiness [
7], headaches [
8,
9], and negative effects on cognition and decision-making [
10,
11,
12]. The acceptable upper limit for the CO
2 concentration in non-industrial buildings in China is 1000 ppm [
13], and ASHRAE standard 62.1-2019 recommends that indoor CO
2 concentrations should not exceed this level [
14]. The outdoor CO
2 concentration typically remains around 400 ppm [
15], posing no harm to human health. However, in enclosed spaces, CO
2 levels can rapidly rise due to human respiration, which can potentially harm human well-being.
The commonly used CO
2 capture technologies are challenging to implement in civil buildings. Absorption is unsuitable indoors due to high energy consumption, the large equipment size, and potential air pollution concerns [
16]. Adsorption exhibits reduced CO
2 adsorption capacity in humid indoor conditions due to the effects of surface water vapor [
17]. Membrane separation faces obstacles in terms of low efficiency at low CO
2 concentrations and high costs [
18]. In contrast, a relatively simple approach involves the introduction of outdoor air to dilute indoor CO
2 concentrations. However, for this approach, the impact of natural ventilation on the thermal comfort of occupants [
19] and the potential introduction of outdoor pollutants into indoor spaces [
20] must be considered. Mechanical ventilation, while effective, requires energy consumption [
21]. Additionally, HVAC systems are necessary to condition the outdoor air for human thermal comfort, which includes processes such as heating, humidification, cooling, and dehumidification. These HVAC processes contribute to approximately half of the energy consumption in HVAC systems [
22,
23]. Therefore, it is crucial to explore energy-saving and sustainable approaches for the reduction of indoor CO
2 concentrations.
Phytoremediation provides an effective method for air purification [
24,
25,
26]. Remarkably, researches in the aerospace field have shown that a closed system integrating plants and humans can achieve a balanced carbon cycle [
27,
28,
29]. However, in civil buildings, the limited space indoors may not allow for a complete balance between plant absorption and human respiration. Nonetheless, the presence of plants can still significantly decrease indoor CO
2 levels. Pegas et al. [
30] placed six plants in a classroom and observed an average decrease in indoor CO
2 concentration from 2004 to 1121 ppm. Tudiwer et al. [
31] found that a classroom with living walls exhibited a 3.5% faster reduction in CO
2 concentration compared to a classroom without plants. Meng et al. [
32] placed living walls in an air-conditioned room and observed a reduction in indoor CO
2 concentration of approximately 10%. Yungstein et al. [
33] observed that the implementation of living walls in actual workplace led to an average decrease of 4.8% in the CO
2 concentration. While qualitative studies have demonstrated the potential of plants in to purify CO
2 in indoor environments, practical implementation remains challenging.
Due to their specific characteristics, office spaces are well-suited for the utilization of the living walls to purify CO
2. In these environments, workers inhale O
2 and exhale CO
2, while plants perform photosynthesis, absorbing CO
2 and releasing O
2, thereby creating a carbon cycle within the confined space [
28]. The working hours of employees [
34] align with the natural light cycle, thus allowing plants to utilize natural light for air purification. Despite the potential impact on human thermal comfort [
35] and equipment aging [
36], areas with concentrated solar radiation in offices are viable locations for the installation of the living walls. Temperatures in offices are regulated to ensure the thermal comfort of employees [
37,
38], and most plants can adapt to air-conditioned rooms [
39,
40]. Furthermore, interaction with plants can enhance productivity of workers [
41]. Shao et al. [
42] observed that 100 heads of
pakchoi could reduce the indoor CO
2 concentration in a 30-m
2 office by 25.7%-34.3%. However, Pennisi et al. [
43] suggested that under office lighting conditions, most plants have limited impact on indoor CO
2 levels. Gubb et al. [
44] found that the influences of dry and wet substrates on the plant CO
2 purification capacity under typical office lighting levels could be ignored, as plants generally fail to reach their LCP. In conclusion, living walls are suitable for CO
2 purification in office spaces, but further research on plant selection, lighting design, and irrigation management is needed to provide practical guidelines.
Living walls that absorb CO
2 can reduce fresh air energy consumption. In office spaces, the occupants' respiration releases CO
2, which can lead to a rapid increase in indoor CO
2 concentration. If left uncontrolled, the elevated release of CO
2 from the respiration of occupants in an office setting can potentially lead to air pollution [
45]. When the concentration of CO
2 released by workers exceeds the required standards, outdoor air is introduced to dilute the indoor CO
2 levels, which results in energy consumption by the HVAC system to process outdoor air. By absorbing CO
2, living walls can decrease the demand for outdoor air and consequently reduce fresh air energy consumption. Torpy et al. [
46] estimated that 15 pots of
Dypsis lutescens could potentially reduce the outdoor air demand by approximately 6%. Parhizkar et al. [
47] found that the incorporation of 5 m
2 of Azolla per person in a typical office building could decrease the outdoor air requirement by about 30%. Shao et al. [
42] demonstrated that 100 heads of
pakchoi could reduce fresh air energy consumption by approximately 12.7%-58.4%. Currently, researchers mainly estimate the fresh air energy-saving impact of the living walls by calculating the balance between the CO
2 absorption rate of plants and the CO
2 generation rate of humans. However, this approach makes it challenging to accurately evaluate the fresh air energy-saving capacity of the living walls. EnergyPlus is a simulation tool capable of calculating the transient building loads required to maintain the temperature and ventilation setpoints for a full year under specific conditions [
48]. Nonetheless, there have been limited studies on the use of EnergyPlus to accurately assess the fresh air energy savings of the living walls.
Based on these reviews, living walls are suitable for indoor CO2 removal and the reduction of fresh air energy consumption in office spaces. This study consists of two main parts, namely (1) the experimental investigation of the impacts of adjustable factors in office spaces on the indoor CO2 removal rate of the living walls, and (2) the simulation-based evaluation of the fresh air energy savings achieved by CO2 removal from living walls under different scenarios. The primary objective of this work is to improve the CO2 removal efficiency of the living walls in office spaces and accurately assess their fresh air energy savings, with the aim of promoting the practical implementation of the living walls.
Figure 1.
The appearance and plan of the experimental room: (a) appearance of the experimental room; (b) settings of the instruments.
Figure 1.
The appearance and plan of the experimental room: (a) appearance of the experimental room; (b) settings of the instruments.
Figure 2.
The living walls in the experimental room: (a) the structure of the living walls; (b) photos of the living walls.
Figure 2.
The living walls in the experimental room: (a) the structure of the living walls; (b) photos of the living walls.
Figure 3.
The plan of the simulated office.
Figure 3.
The plan of the simulated office.
Figure 4.
The changes in the indoor CO2 concentration (a) before the ventilation turns on, (b) during working hours with a VAV system, (c) after the CAV system turns on, (d) and during working hours with a CAV system. Note: C1 is the initial CO2 concentration, Cst is the steady-state CO2 concentration, and CU and CL respectively denote the upper and lower limits of the CO2 concentration of the CAV system.
Figure 4.
The changes in the indoor CO2 concentration (a) before the ventilation turns on, (b) during working hours with a VAV system, (c) after the CAV system turns on, (d) and during working hours with a CAV system. Note: C1 is the initial CO2 concentration, Cst is the steady-state CO2 concentration, and CU and CL respectively denote the upper and lower limits of the CO2 concentration of the CAV system.
Figure 5.
The division of the Climate Region of Building in China and typical cities.
Figure 5.
The division of the Climate Region of Building in China and typical cities.
Figure 6.
The mean CO2 concentration (%) changes from the input concentration (1000±100 ppm) within 2 hours under different conditions: S. trifasciata (S), E. aureum (E), Dry (D), Wet (W), High light intensity (H), Medium light intensity (M), Low light intensity (L), Dark (DA). Shaded areas represent the SEM (n = 3).
Figure 6.
The mean CO2 concentration (%) changes from the input concentration (1000±100 ppm) within 2 hours under different conditions: S. trifasciata (S), E. aureum (E), Dry (D), Wet (W), High light intensity (H), Medium light intensity (M), Low light intensity (L), Dark (DA). Shaded areas represent the SEM (n = 3).
Figure 7.
The CO2 removal rates are presented as the mean ± SEM (n=3). Notes: lowercase letters indicate significant differences (p=0.05).
Figure 7.
The CO2 removal rates are presented as the mean ± SEM (n=3). Notes: lowercase letters indicate significant differences (p=0.05).
Figure 8.
The light response curve of the E. aureum living walls in a wet substrate.
Figure 8.
The light response curve of the E. aureum living walls in a wet substrate.
Figure 9.
The variations of the CO2 concentration in the offices with VAV or CAV systems, with different numbers of occupants, and with or without living walls, on a typical working day.
Figure 9.
The variations of the CO2 concentration in the offices with VAV or CAV systems, with different numbers of occupants, and with or without living walls, on a typical working day.
Figure 10.
The fresh air volumes in the offices with VAV or CAV systems, with different numbers of occupants, and with or without living walls on a typical working day.
Figure 10.
The fresh air volumes in the offices with VAV or CAV systems, with different numbers of occupants, and with or without living walls on a typical working day.
Figure 11.
The annual energy consumption for outdoor air cooling and heating in the offices with VAV or CAV systems, with different numbers of occupants, and with or without living walls, in typical cities.
Figure 11.
The annual energy consumption for outdoor air cooling and heating in the offices with VAV or CAV systems, with different numbers of occupants, and with or without living walls, in typical cities.
Table 1.
The instruments used in the tests.
Table 1.
The instruments used in the tests.
Instrument |
Model |
Parameters |
Accuracy |
Setting Points |
Air quality monitor |
SenseAir S8 |
CO2 (ppm) |
±40 ppm |
Indoor: In the center of the room, 1.2 m above the ground |
SensenSHT20 |
Temperature (°C) |
±0.3 °C |
Relative humidity (%) |
±3% |
Photosynthetic photon flux density (PPFD) meter |
Apogee MQ-500 |
PPFD/(μmol·m-2·s-1) |
±5% |
On the top of canopy |
Apogee SQ-520 |
Outdoor: Roof |
CO2 sensor |
RS-BYH-CO2-M |
CO2 (ppm) |
±40 ppm (25 °C) |
Outdoor: Roof |
Weather station |
Campbell 81000 |
Wind speed (m/s) |
±1% |
Outdoor: Roof |
Campbell CS215 |
Temperature (°C) |
±0.3 °C (25 °C) |
Relative humidity (%) |
±2% (25 °C) |
Volumetric water content (VWC) sensor |
Decagon Devices 5TE |
VWC (m3/m3) |
±3% |
Substrate |
Table 2.
The characteristics of the plant species selected for experiments. The leaf area and plant height (n = 6) are presented as the means ± standard error of the mean (SEM).
Table 2.
The characteristics of the plant species selected for experiments. The leaf area and plant height (n = 6) are presented as the means ± standard error of the mean (SEM).
Species |
Family |
Metabolism |
Leaf Type |
Leaf Area (cm2 ) |
Plant Height (cm) |
Sansevieria trifasciata |
Asparagaceae |
CAM |
succulent |
537±77 |
28±1 |
Epipremnum aureum |
Araceae |
C3
|
herbaceous |
614±111 |
22±1 |
Table 3.
The outdoor meteorological parameters of typical cities in different climate regions [
51].
Table 3.
The outdoor meteorological parameters of typical cities in different climate regions [
51].
Climate Region |
City |
Average Temperature in Winter (°C) |
Dry Bulb Temperature in Summer (°C) |
Relative Humidity in Summer |
Atmospheric Pressure in Summer (kPa) |
Moisture Content in Summer (g/kg) |
Enthalpy in Summer (kJ/kg) |
Ⅰ |
Harbin |
-27.1 |
30.7 |
62% |
98.8 |
17.7 |
76.2 |
Ⅱ |
Beijing |
-9.9 |
33.5 |
61% |
100.0 |
20.2 |
85.7 |
Ⅲ |
Shanghai |
-2.2 |
34.4 |
69% |
100.5 |
24.1 |
96.5 |
Ⅳ |
Guangzhou |
5.2 |
34.2 |
68% |
100.0 |
23.6 |
95.0 |
Ⅴ |
Kunming |
0.9 |
26.2 |
68% |
80.8 |
18.3 |
73.0 |
Ⅵ |
Lhasa |
-7.6 |
24.1 |
38% |
65.3 |
11.0 |
52.4 |
Ⅶ |
Urumqi |
-23.7 |
33.5 |
34% |
91.1 |
12.2 |
65.2 |
Table 4.
The confirmation results of the two experimental rooms.
Table 4.
The confirmation results of the two experimental rooms.
|
Date |
Wind Speed (m/s) |
Leading Wind Direction |
Outdoor and Indoor Temperature Difference (°C) |
CO2 Concentration (ppm) |
CO2 Concentration Difference (ppm) |
Room A |
Room B |
Room A |
Room B |
1 |
2022/10/14 11:00-13:00 |
2.3 |
WSW/SSW/WNW |
4.1 |
3.4 |
150 |
171 |
21 |
2 |
2022/10/15 0:00-2:00 |
2.3 |
WSW/SSW |
4.6 |
3.5 |
47 |
49 |
2 |
3 |
2022/10/16 10:30-12:30 |
4.6 |
WSW/SSW |
4.9 |
3.8 |
164 |
182 |
18 |