1. Introduction
Double skin façades (DSF), also known as ventilated cladding systems, are a widely used construction method in the building industry, employed in both new construction projects and building refurbishment [
1]. DSF have become popular in contemporary building design due to their energy-efficient and visually appealing characteristics. This façade solution involves the installation of vertical or horizontal elements anchored to the structural and non-structural components of a building, upon which an external cladding is mounted, creating a ventilated air cavity whose dimensions depend on the spacing between the outer cladding elements.
In DSF, the importance of analysing the impact of dynamic loads on both structural and non-structural components cannot be overstated. This evaluation is crucial in ensuring the safety and integrity of the whole building and its occupants under various conditions, including normal service conditions and extreme loads resulting from events such as windstorms, earthquakes, or explosions [
2,
3]. While structural elements often receive primary attention due to their role in maintaining the stability of a building, non-structural elements such as internal partitions, façades, and windows also warrant significant consideration [
4]. These elements not only constitute a major portion of construction costs but also require careful evaluation to ensure their optimal performance. To assess the capacity of non-structural components and connections, it is recommended to implement both analytical and experimental programs [
5,
6]. Such evaluations typically fall outside the purview of building codes. Although these codes do provide guidance on estimating minimum design forces, more specialized methodologies or experimental testing may be necessary for complex systems. These additional measures serve dual purposes: they enhance our understanding of the performance and strength of these components, and they help determine whether forces exceeding those specified in building code requirements are possible. This dual approach ensures a comprehensive understanding of both structural and non-structural elements, ultimately contributing to safer and more resilient buildings. The construction process of DSF includes the different stages: Substructure´s supporting members, consisting of vertical and/or horizontal elements that are attached to both the structural and non-structural elements of the building. These elements serve as the framework for the cladding system. Exterior cladding, a durable external cladding material is affixed to the framework. This outer layer not only protects the building from environmental factors but also plays a crucial role in the aesthetics of the structure. And air cavity formation, the gap between the external cladding and the structural element of the building creates an air cavity. The dimensions of this cavity are determined by the spacing between the exterior cladding components. This cavity allows for natural ventilation and acts as a thermal buffer.
In contemporary architectural practices, increasingly complex façade systems as DSF entail innovative solutions that consider several critical structural factors as: a) Massiveness: The overall volume and spatial arrangement of the building can significantly influence the design and performance of the façade. b) Flow Characteristics: The façade’s permeability or continuity can lead to the generation of vortices or turbulence, impacting the building’s thermal and acoustic comfort. c) Material Selection: The use of heavy materials such as stone, masonry, glass, and steel can affect the façade’s structural integrity and aesthetic appeal. And d) Complex Geometries: The incorporation of intricate elements such as perforated elements, panels, tiles, and veneers can result in unexpected responses due to their interaction with environmental factors. Therefore, a comprehensive understanding of these factors is essential for designing effective and sustainable façade systems. A recent alternative of DSF involves the use of flexible elements to support the external cladding components [
7]. This variant introduces an innovative approach to the traditional construction method, offering distinct advantages, among them: Adaptability, given that flexible elements can accommodate irregularities in the building's structure, allowing for more versatile and creative designs [
8]. Also, a better dynamic response, since the flexibility of these elements enables the cladding system to adapt to external forces, such as wind loads or seismic activity, without compromising its integrity [
9,
10,
11,
12]. And, often, an enhanced insulation, because by incorporating flexible elements, the insulation properties of the cladding system can be improved, further enhancing the building's energy efficiency [
13].
Regulatory frameworks play a crucial role in ensuring the safety and performance of DSF. However, usually these regulations often focus primarily on structural elements or provide general requirements for various façade components [
7,
14]. The validation of DSF involves a comprehensive examination of their components, performance, and interactions. This process generally encompasses different means: Finite Element Modelling (FEM) and calculation tools that are indispensable for analysing the performance of building systems. Also, laboratory tests that are essential for assessing the physical properties and performance of building components. And pilot-scale testing that involve the construction and evaluation of small-scale and full-scale building prototypes. These prototypes replicate key aspects of the system and allow researchers to assess its performance in a practical setting. Pilot-scale tests provide valuable data on factors such as structural integrity, energy efficiency, and occupant comfort. The whole validation process aims to ensure that the system meets regulatory requirements while also accommodating innovative design approaches and materials.
Most studies available in the scientific literature are related to the lighting control and/or energy efficiency performance of DSF systems. Examples of this approach are the works of Hoffman et al. [
15], Rizki et al. [
16], or Yun et al. [
17]. In recent years, the optimisation of both functions has started to be based on statistical models proposing different algorithms to improve the design features of these façades [
18,
19]. Recent scientific literature has highlighted the use of the Finite Element Method (FEM) in the analysis of DSF. For instance, a study conducted by Camilla Lops et al. [
20] used Computational Fluid Dynamics (CFD), a subset of FEM, to simulate the behaviour of naturally ventilated double skin facades. The study compared various double facade configurations by adopting bi- and three-dimensional domains and different turbulence models. In another study, Süleyman İpek & Esra Mete Güneyisi [
21] used FEM to simulate the behaviour of concrete-filled double skin steel tubular (CFDST) composite columns having a circular hollow section. In addition to these, there are several other studies that have utilized FEM for analysing ventilated facades and double skin systems. These include studies by Choi W, Joe J, Kwak Y, Huh JH [
22], which provide valuable insights into the application of FEM in this field. These studies demonstrate the potential of FEM in analysing complex building systems such as ventilated facades and double skin systems. However, more research is needed to fully understand and optimize these systems’ performance under various conditions.
While there is extensive research on the energy efficiency performance of DSF, studies on the structural performance of heavy ventilated cable-supported facades are limited. The interplay between wind and earthquake loads with permeable DSF can be critical, especially when the input load frequency aligns with the facade’s natural frequency, leading to a resonance phenomenon. This paper aims to address this research gap by presenting the results of an experimental program designed to assess the performance of such non-structural components under lateral loads. The evaluation methodology encompassed laboratory and full-scale tests to ascertain the dynamic properties of the facade and estimate the capacity of individual components and the overall system, analysing especially those loads which, by their nature, require full-scale prototypes, namely loads and deformations due to seismic, wind and impact effects of particular interest in non-rigid façade systems. The applied methodology is also intended to guide the system-testing iteration and its usefulness in the design process. This work aims, therefore, to delve into the study, evaluation, and validation of a cable net suspended DSF. Two of the main goals of the research are collecting and correlating the results of the experimental evaluation conducted on the DSF system, and to perform simulations and experimental procedures based on different evaluation guides for DSF elements and the necessary adaptation to apply them to the case study analysed.
2. Materials and Methods
2.1. Methodology Overview
The methodological process of this research is divided into 5 phases. In the first one, the elements of the system are designed and defined. Once an adequate degree of suitability has been reached, in the second phase the regulatory requirements of the system and its components are studied and checked. In the third phase, a test plan is completely defined to evaluate the system performance at both, component level and constructive system levels. During the fourth phase, the guidelines indicated in the test plan are executed, including component testing under reference standards or by adapting some test procedures due to the uniqueness of some elements. In addition to the characterization of individual components, tests are also carried out to check the interaction and compatibility between elements, as well as full-scale experimental tests of the complete system. The whole process of building full-scale experimental prototypes for testing also allows a real evaluation of the whole construction process foreseen for the system and a redesign, if necessary, in case of unforeseen events. The fourth phase is complemented by the possibility of carrying out computer simulations to check the suitability of elements or to extrapolate the experimental results to other situations that have not been possible to test on a real scale due to the great variety of possible solutions. The fifth phase is the last phase of the methodology. In this phase, all the results obtained in previous phases are collected, studied and it is decided whether they are viable based on objective parameters and how the system is evaluated, positively or negatively. It may also happen that a negative evaluation leads, in a cyclical way, to a redesign of elements in the first phase. The diagram displayed in
Figure 1 shows the methodology used throughout the design and validation of the DSF system and which could be applicable to the improvement process of other similar building façade systems. This work is focused on the actions referred to in the fourth and fifth phases, as well as the regulations applicable to the execution of the tests necessary to characterize the ventilated façade system. In the development of the text, the actions related to wind, seismic and external impact tests are described. The characterization values of the individual components and the interaction between them are also indicated, specifying the regulations under which they have been tested.
2.2. DSF Case Study
In order to clearly describe the system, in addition to the description of components, several images of the different parts of the system are presented in this section. The DSF system analysed as case study is based on the assembly of small-sized ceramic tiles on a framework of vertical cables fixed to horizontal U-profiles, which are responsible for supporting the weight of the ceramic pieces, as well as the traction of the cables. The vertical wiring is used to insert and fix the position of the ceramic pieces, as well as to transmit the actions on the outer skin to the horizontal profiles which are responsible for transmitting the loads to the supporting structure, together with the support brackets on which the horizontal profiles are fixed. Together with these elements, retaining devices are installed to absorb the pressures and suction generated by the wind load on the façade (Figure 2). In addition to these characteristic parts of the system, a series of auxiliary elements are designed which are necessary for the correct assembly of the system, specifically L-shaped profiles which are placed at the crown of the façade and which, once the wall panel is completed, are removed so that they can be reused in a different panel.
Figure 2.
DSF system view. (a) 1. Thermal insulation in ventilated chamber, 2. Horizontal stainless-steel U-profiles for support, 5. Auxiliary assembly profiles, 6. Supporting brackets, a. Retaining device without anchoring plate, b. Retaining device with anchoring plate in place, c. Special ceramic pieces for profile closure. And (b) Full-scale set-up view.
Figure 2.
DSF system view. (a) 1. Thermal insulation in ventilated chamber, 2. Horizontal stainless-steel U-profiles for support, 5. Auxiliary assembly profiles, 6. Supporting brackets, a. Retaining device without anchoring plate, b. Retaining device with anchoring plate in place, c. Special ceramic pieces for profile closure. And (b) Full-scale set-up view.
Figure 3.
(a) Section of the DSF system: 1. base plate, 2. base plate retainer, 3. base plate closing penultimate row, 4. base plate closing last row, 5. base plate cladding, 11. stainless steel cable, 12. aluminium end cap, 15. Stainless steel U-profile, 18. Supporting brackets, 20. Fixing assembly, 21. Anchoring to concrete elements, 22. Wind retention assembly, 25. Supporting structure, 26. Non-structural vertical facing, and 27 Thermal insulation. And (b) DSF rear view.
Figure 3.
(a) Section of the DSF system: 1. base plate, 2. base plate retainer, 3. base plate closing penultimate row, 4. base plate closing last row, 5. base plate cladding, 11. stainless steel cable, 12. aluminium end cap, 15. Stainless steel U-profile, 18. Supporting brackets, 20. Fixing assembly, 21. Anchoring to concrete elements, 22. Wind retention assembly, 25. Supporting structure, 26. Non-structural vertical facing, and 27 Thermal insulation. And (b) DSF rear view.
Figure 2.
Ceramic tiles that constitute the construction system: (a) Standard tile, (b) Retaining tile, (c) Closing tile, and (d) Special corner tile.
Figure 2.
Ceramic tiles that constitute the construction system: (a) Standard tile, (b) Retaining tile, (c) Closing tile, and (d) Special corner tile.
The construction system components are therefore grouped into the following categories: Shaped ceramic tiles set (
Figure 4), which integrates all the possible pieces to be installed on the cable-net framework; Supporting device, which contains all the necessary elements to support the ceramic pieces, such as cables, horizontal profiles, etc.; Retaining device, responsible for supporting the action of the wind on the surface of the façade; and all the auxiliary components, necessary for the correct assembly of the system on site (
Figure 5).
Figure 3.
Components of the system: (a) Ceramic elements, (b) Supporting device, (c) Retaining device, and (d) Auxiliary components.
Figure 3.
Components of the system: (a) Ceramic elements, (b) Supporting device, (c) Retaining device, and (d) Auxiliary components.
2.3. Experimental characterization of materials and system features.
To determine the components features specifically designed for the system, the different constituents have been characterized and tested: ceramic parts, stainless steel metal elements, anchors, etc., in accordance with the applicable regulations, and depending on the specific requirements in each case, considering that, when necessary, the tests have been adapted (
Table 1). Based on this process and depending on the results obtained, feedback and redesign is carried out based on the detection and resolution of critical points detected during the characterization of the different elements.
In the test-driven design process, the following phases have been carried out: 1. Adaptation and design of experimental test procedures according to façade system regulations. 2. Design and manufacture of auxiliary elements for testing. 3. Trial and error tests according to the dissimilar materials and geometries available for non-ceramic components, and initial evaluation of compliance of each one of them. 4. Testing plan final definition and implementation. 5. Redesign-oriented feedback for the non-ceramic components, based on critical points detected during the execution of tests. This last phase is effective in addressing non-compliance with the stresses to which they are exposed according to regulatory requirements. For instance, based on the results obtained, the type of stranded cable, cable terminals and cable-terminal joints have been redesigned.
2.4. Wind Load Testing
The requirements to cope with the action of wind loads are generally defined in the Spanish regulation Technical Building Code (Código Técnico de la Edificación, CTE) in the basic document on Structural Safety, Actions in Buildings (CTE-DB-SE-AE) [42] as the application of pressure and suction loads distributed over the surface of the building that respond to the distribution and value of the pressures exerted by the wind on a building and the resulting forces depend on the shape and dimensions of the building, the characteristics and permeability of its surface, as well as the direction, intensity and gustiness of the wind. Although the Spanish regulations establish the requirements in terms of load values that the building, and therefore its external skin, must withstand, they do not specify the methodology to be followed to assess these properties. For this reason, the indications given in the European Technical Approval Guidelines (ETAG) and the European Assessment Documents (EAD) are employed; for the evaluation of wind performance, the indications given in ETAG 034 [38,39], and the EAD 090062-00-0404 [43].
The sample has been tested as defined in section 5.4.1.1 of ETAG 034 [38] for wind suction resistance tests for ventilated façade kit. The test consists of applying wind loads at different pressure steps. Two initial pulses of 300 Pa, 1 pulse of 500 Pa, 1 pulse of 1000 Pa and the rest of the steps increasing the pressure by an additional 200 Pa are applied. Each step has a duration of at least 10 seconds (
Figure 6). After the application of each load step, the wind pressure is stopped, and a new load cycle is started. During the application of the pressure, the reading of the displacement transducers on the sample and the residual deformation of the displacement transducers 1 minute after the end of the pressure step are recorded. Any damage is also noted. The test continues until the deformation produced is irreversible and causes a malfunction of the lining system or if collapse occurs.
Figure 4.
Example of wind load design [43].
Figure 4.
Example of wind load design [43].
2.5. Earthquake Testing
DSF and other traditional non-load-bearing cladding systems are construction techniques for covering and finishing building parts that are considered as non-structural elements. This means that they are only considered as gravity loads for structural calculations, although the situation becomes different when analysing the effects of dynamic loads. These elements influence the strength, damping, hysteresis, and deformation of the building [40]. The existing Spanish standard NCSE-02 [44] refers exclusively to claddings, interior partitions, false ceilings, and other elements, such as façade panels, etc., all of them must be properly bonded to structural elements to avoid the detachment of parts during seismic shaking, especially if the ductility of the construction is assumed to be high or very high. In addition, in transit areas, the fixing of cladding and the anchoring of cladding or other façade elements shall be carried out with highly durable materials and by appropriate techniques to prevent the detachment of parts in the event of an earthquake. Emphasis is placed on the risk derived from the detachment of façade elements due to inadequate fixing, considering as such the exclusive use of chemical joints, indicating that mechanical fixings by means of metallic elements are considered appropriate [42].
It was considered necessary to know the system performance against the earthquake dynamic action, so a test and loading protocol was followed based on the proposals of FEMA 461 [41] and the study carried out in the article "Experimental study on the response of seismically isolated masonry infilled steel frames during the initial stages of a seismic movement" by Pallarés et al. [40]. A horizontal cyclic load is applied to the upper beam of the portal frame (loading and unloading) which houses the ventilated façade leaf and a rear brickwork cladding, which simulates the conditions against a seismic load in a real situation. The operator that applies the load and thus generates the cycles has a capacity of up to 500 kN and is responsible for increasing the displacements at the head of the gantry by applying an increasing force at each cycle. For more detailed information on the process see
Appendix A,
Table A3. The main characteristics of the test are defined below:
- -
There is a protocol where the monitored quantity is the displacement.
- -
Each cycle (cyclic load applied) is composed of two sub-cycles. The first is the so-called noval sub-cycle and is composed of four sections: a) First section. The gantry is pushed to the right until the target displacement is reached in the load cell. b) Second section. The gantry is pulled to the left until it returns to the initial position. c) Third section. The gantry continues to be pulled to the left until the same displacement as the first section is reached in the load cell, but in the opposite direction. And d) Fourth section. The gantry is pushed back to the initial position. For more information see
Appendix A Figure A1.
- -
In the second sub-cycle, known as the reloading sub-cycle, the same operations are repeated as in the first noval sub-cycle with the same target displacement.
2.6. Safety in Use: Exterior Impact Testing
The Spanish regulatory framework follows the requirements established in the Technical Building Code, which does not establish a minimum performance that ventilated façade systems must guarantee in relation to resistance to external impacts [42]. The regulation is the same for internal partitioning systems, which are also assessed against impact situations and eccentric vertical loads to ensure safety in use, although there are no national regulations in this respect [45]. The European standard establishes through the Construction Products Regulation no. 305/2011 (CPR) that systems can obtain the CE mark if they are assessed according to the European Technical Approval Guidelines (ETAG) or through the European Assessment Documents (EAD) [
25]. In the case of impact assessment, it is used ETAG 034 [38,39] later converted into EAD 090062-00-0404 [43].
Tests are based on the application of an impact energy on the façade sheet. The energy transmission is done using both, a hard body, and a soft body, which resemble the impact of a small but hard object (e.g., hail or stones) and the impact of a larger but soft object (e.g., a falling person). Thus, the façade system performance is evaluated and classified according to a category of use depending on the joules of energy supported. The category of use establishes the locations where the evaluated system could be placed depending on whether they are accessible, heavily used, public, private, high, etc. For more detailed information see
Appendix A,
Table A4.
In addition, following the ITeC criteria, a sub-classification is added that allows façades to be categorized as easily replaceable or repairable products if they can maintain their position on the façade when they have broken due to the effect of an impact, without allowing them to fall after breakage [46]. In this way, the energy values of impacts on the façade are reduced, allowing products that are in principle more fragile to access better categories of use. For more detailed information see
Appendix A,
Table A5.
3. Results and Discussion
3.1. Wind Load Assessment
Once the individual characteristics of each of the components have been evaluated, the performance under wind loads is studied, especially when they could compromise the functioning of the façade system. An experimental laboratory test was carried out on a real scale of a suitably size to test different configuration cases. Once the experimental test has been carried out, several simulations are performed using finite elements (FE) to check and validate the interaction of the ceramic pieces with the vertical metal wiring, characteristic of the system when it receives wind loads, as well as the behaviour of the point anchors that are distributed along the surface of the façade, known as retaining devices (Figure 3c) and whose purpose is to support these actions on the surface of the façade.
Case study is designated as a ventilated façade ceramic exterior cladding kit according to ETAG 034 [38], with dimensions 1820 × 1720 mm2 (W x H), with a ceramic surface area of 3.13 m
2 in a normal arrangement (60 mm spacing between cables) for the supporting devices. To simulate real on-site installation conditions, the samples were installed on a steel tube perimeter support frame with vertical profiles of 100 × 80 × 6 mm and shaped top and bottom profiles of 100 × 120 × 4 mm welded on a profile of 100 × 40 × 4 mm. Two welded steel tube uprights, a horizontal and a vertical cross member of 100 × 60 × 6 mm are added to simulate the anchoring arrangement on site, as shown in
Figure 5.
Figure 5.
Perimeter and support frame for testing: 1. Profile composed of two welded tubular profiles type RHS 120.100.1 and 40.100.4; 2. Tubular profile RHS 80.100.4; 3 and 4. Tubular profile RHS 100.60.6; 5. Yellow lines, continuous seam welding in the workshop; Blue markings, retaining device/m2; Red markings, 2 retaining devices/m2. All dimensions are in millimetres.
Figure 5.
Perimeter and support frame for testing: 1. Profile composed of two welded tubular profiles type RHS 120.100.1 and 40.100.4; 2. Tubular profile RHS 80.100.4; 3 and 4. Tubular profile RHS 100.60.6; 5. Yellow lines, continuous seam welding in the workshop; Blue markings, retaining device/m2; Red markings, 2 retaining devices/m2. All dimensions are in millimetres.
The specimen is installed in a K. Schulten Fenstertechnik model KS 4040/650 PC with manual clamping cylinders [47]. To improve the air tightness of the specimen, so that the appropriate pressure can be generated in the test rig, the inner side is covered with a non-air-permeable foil, leaving sufficient clearance so that it cannot influence the specimen performance during the test. In this way, the specimen becomes airtight, preventing leakage between the joints of the ceramic pieces. The lateral space between the sample and the supporting structure is closed with two "L" profiles screwed to the structure (
Figure 6).
Figure 6.
Test sample: (a) Metal frame on which the ventilated façade is mounted; (b) Façade panel installed on the metal frame and with L-profile perimeter enclosure.
Figure 6.
Test sample: (a) Metal frame on which the ventilated façade is mounted; (b) Façade panel installed on the metal frame and with L-profile perimeter enclosure.
To record the displacements during test, linear measurement transducers are implemented. Two different displays are used, one for configurations 1 and 2 and a second for configuration 3. This is due to the varying distance between the wind retaining elements and the different position of the measuring transducers. One of them in the middle of the horizontal between retaining devices (A1 and B1); a second one on a retaining device forming the previous horizontal (A2 and B2); a third one on half of the vertical joining a retaining device (A5 and B5); a fourth one on a retention device forming the previous vertical (A3 and B3); a fifth one on the crossing between vertical and horizontal traced (A4 and B4) and, finally, a sixth one on the half of the diagonal joining (
Figure 7).
For configurations 1 and 2, similar results have been obtained in terms of displacement under load and residual deformation when the load is no longer applied. The displacement produced in these cases is small, around 20 mm, and once load ceases, the pieces recover their original position. In the case of configuration 3, higher values of displacements are achieved since the proposed configuration of retention devices allows a greater displacement of the façade skin, around 70 mm for 3200 Pa of pressure (
Figure 8).
Following the criteria described for the sensors display, a complete sector of the sample is accurately monitored and, since the pressure is assumed to be homogeneous and fully symmetric on the vertical and horizontal axes, it is possible to know the values produced on the rest of the surface. Knowing these values, it is possible to represent the most unfavourable situations of each of the configurations and to obtain, by means of a horizontal section (
Figure 9) and a vertical section (
Figure 10), the deformations produced during the test on the ceramic skin.
Results obtained during the execution of the tests are considered satisfactory, with the sample reaching 1800 Pa of pressure (1.8 kN/m
2) with no defects in either the ceramic or metallic elements. During the execution of the test for configuration 1, breakage of ceramic pieces near the retaining devices occurred. In the repetition for configuration 2, breakage occurs in 1 piece at 1800 Pa (1.8 kN/m
2) and in 3 pieces at 2200 Pa (2.2 kN/m
2), although the test continues up to 2400 Pa (2.4 kN/m
2), matching the test for configuration 1. During the execution of configuration 3, breakage of the first ceramic pieces occurs at 2800 Pa (2.8 kN/m
2) and the test continues up to 3200 Pa (3.2 kN/m
2), the upper limit of the test chamber. The ceramic skin has showed flexibly, as expected, with breakage occurring in the configurations with a greater number of retention devices and therefore less flexibility. It should be noted that, although there was breakage of parts, there was no detachment from the plane of the façade, as they remain locked with the metal cables (
Figure 11). For more detailed information see
Appendix A,
Table A6 and
Table A7.
Prior to carrying out the tests, a theoretical model was developed to determine the façade cabling performance with the main objectives of understanding its functioning and developing a calculation abacus of possible situations in which the system could be installed depending on the location of the target building. In
Figure 12, the curves in the graph represent the deformation of a cable for different wind pressures. The comparison between the experimental deformation of the central cable (dashed lines) and the deformation obtained by theoretical calculation (continuous lines) considering a separation between retaining anchors of 1 m is shown.
The resulting conclusion is that the theoretical model does not reproduce the coercion generated by the ceramic pieces and, therefore, reduce the deformation at the intermediate point, as does occur in the execution of the test according to the data obtained. The theoretical deformations produced greater deformations than the experimental ones, thus being on the safe side.
However, although these results have a margin of security, the theoretical model was adjusted by fitting the results obtained in different cable configurations with the most unfavorable values from the experimental tests. The result is shown in
Figure 13, where the theoretical model reproduces the experimental results more adequately. In any case, the theoretical model continues to provide higher values compared to the experiment and therefore offers more reliable values.
3.2. Earthquake Response Assessment
The DSF case study performance assessment during an earthquake event was carried out experimentally as part of the façade characterization tests, on a full-scale test specimen built in the laboratory. The objective consisted of testing the performance of a ventilated façade of the system, built on a concrete portal frame filled with traditional brick masonry elements, similar to the most common construction types in Spain [48].
The sample built for the test represents an intermediate portico of a building and it is constituted on the basis of 3 essential parts: 1. Concrete frame, responsible for receiving the cyclic thrusts and tractions, as well as supporting the rest of the elements; 2. Pre-existing enclosure, consisting of a traditional façade with a double brick façade and hollow bricks cladding, both brick walls free of seismic insulation systems (
Figure 14); 3. Outer sheet of the ventilated façade system, consisting of small ceramic elements and vertical cable mesh in its usual configuration as showed in Figure 2.
The frame, a reinforced concrete portal frame consisting of two beams and two 30 x 30 cm square columns, 3 m high and 3 m wide. The frame is fixed to the foundation slab by means of two joints at the lower ends of the columns. Each of these elements is reinforced both longitudinally and transversely to withstand the stresses simulated during the test. The so-called pre-existing enclosure is a 2.7 × 2.7 m
2 double-brick wall confined within the reinforced concrete frame. It simulates the stiffening performance of vertical separations within multi-story arcade structures. It is composed of several layers: A. 11.5 cm white klinker facing brick with 1 cm thick M7.5 mortar joints; B. 1 cm thick cement mortar filling on the inside face of the facing brick leaf; C. 3 cm unventilated air space; and D. a 7 cm double hollow brick (
Figure 14).
The third part of the sample installation corresponds to the ventilated façade sheet executed dry and with stainless steel wire mesh corresponding to the system developed, with a total of 64 rows with 12 platelets for each one (
Figure 15).
Since during the test execution usually occur unexpected events that are not visually controlled in the hidden parts of the specimen, the sensors’ location is carefully planned to check the state of the concrete frame and the pre-existing brickwork leaves. These walls are also partially hidden behind the ventilated façade panel on the outside face. For more detailed information see
Appendix A,
Table A2.The whole loading protocol establishes 15 cycles of cyclic loading (
Table A1), however, if during the development of the test there are evident signs of failure or collapse of the sample, the procedure is stopped, and the test is terminated. In this case, the test was stopped at the completion of cycle number 13, after the collapse of the hollow brick inner leaf and after having followed the standard protocol cycles, for more detailed information see
Appendix A,
Table A3. The graphical display of these cycles is showed in
Figure 16.
As already specified, the test process is stopped at iteration number 13 due to the existence of considerable damage in parts 1 and 2 of the sample, i.e., in the double brick sheet, similar to a traditional façade. The magnitude of the damage can be seen in
Figure 17. The proportions of these damages prevent from continuing with the standard progress of the cycles, so it was decided to stop the procedure and conclude the test.
During the execution of the test, the ventilated sheet performance consists of the displacement of the plane of the sample from left to right, following the movement of the concrete frame according to the moment of the cycle in which it is found. As the system has a certain degree of freedom in the face of loads, the ceramic tiles adapt to the new positions imposed by the movement of each of the cycles and there are hardly any small defects visible to the naked eye.
The damage assessment at the ventilated façade level covers both the verification of ceramic and non-ceramic elements. This distinction is made because ceramic elements are understood as a non-structural cladding, in which the replacement of affected parts after a hypothetical earthquake is at the discretion of the risk that may exist against the detachment of small debris, but not because the overall stability is compromised as it would be in the case of non-ceramic elements. The damage to the ceramic skin is limited to small flaws, chipping or breakage of pieces that appear as cracks, but without any detachment of rubble at any time (
Figure 18). In the non-ceramic elements, it has been checked that there is no appreciable damage by visual inspection, paying special attention to the position of each element at the beginning and end of the test, with no damage to the support device or the wind retention device (
Figure 19).
As key points of the earthquake test assessment on the ventilated façade panel, the following conclusions can be stated: 1. Damages derived from the action of the earthquake on the traditional walls are produced, as well as detachments in both brick walls and total collapse in the interior cladding leaf; 2. The concrete frame, reproducing an intermediate floor, is fatigued and cracked, thus reducing its resistance capacity and its useful life (
Figure 20). 3. The cladding executed with the ventilated façade system is complete once the test has been concluded, with only small cracks that are not very noticeable in most cases and can be easily repaired by replacing parts. 4. In relation to the amount of surface area covered, the percentage of cracked pieces is very low and no pieces of ceramic tile or falling debris originating in the ventilated façade have fallen off.
3.3. Impact Assessment
A sample of dimensions 1820 x 1720 mm
2 (width x height) was used for the impact test, using the steel frame manufactured for the wind test and applying the same standard arrangement of ceramic tiles with wire spacing every 60 mm (
Figure 5). The devices used as impact means are 2 steel balls of 0.5 kg and 1 kg as hard bodies and two bags of 3 kg and 50 kg as soft bodies (
Figure 21).
The sample was tested as defined in section 5.4.4 of ETAG 034 [38], as well as the ITeC criteria [46] for ventilated façade systems that allow replacement. The criterion used is to first perform all hard body impacts by replacing the impacted parts with untested parts, before moving on to the next loading step. The hard body impacts are carried out according to the following criterion: First impact in a centred position on a ceramic piece, second impact on the vertical between two pieces and third impact at a point where three pieces meet, without using previously impacted ceramic pieces in each of the repetitions. For the soft body impacts, the criterion of carrying out the different collisions both in the areas close to the retainers and in those further away is followed, with the aim of testing and comparing the sample performance in different confinement conditions, both cable and ceramic tiles (
Figure 22). The procedure for handling the impact bodies is shown in
Figure 23.
Following the above criteria, the impacts are performed by energy steps and with the impact of the hard body on the ceramic skin (
Figure 25): First impact performed H1, of 1 J with 0.5 kg hard body, a drop height of 0.20 m and three repetitions. It causes through cracks in the ceramic elements that can be seen on the back of the piece, but no pieces are detached (
Figure 24a,b). With the same energy, a repetition of the H1R impacts is carried out in other locations, with the same result. Second impact H2, of 3 J with a hard body of 0.5 kg, a drop height of 0.61 m and three repetitions. It causes through cracks with detachment and twisting of impacted ceramic elements (
Figure 24c,d). For the same impact energy H2R, a repetition of three impacts is carried out with the same result. Results obtained for the impacts with the 0.5 kg hard body led to a decision not to continue at higher energies as the 3 J impacts determined that the test for this body should be stopped. The test continues with the soft body impact: First impact performed S1, 10 J with a 3 kg soft body, a drop height of 0.34 m and three repetitions. No damage to the ceramic elements (
Figure 24c). Second impact S2, 60 J with a 3 kg soft body, a drop height of 2.04 m and three repetitions. It produces through breaks in the ceramic pieces, allowing, in some cases, the cracked elements to rotate on the braided cable. No detachments occur (
Figure 24d).
The analysis of the results of the tests carried out to determine the safety of use against external impact shows that the ventilated façade system withstands soft-body impacts without deterioration, which allows a Category IV classification as prescribed in Tests based on ETAG 034 [38,39]. On the other hand, the impacts carried out using a hard body indicate the fragility of the ceramic pieces against this type of impact. However, as it is a system in which the replacement of pieces is simple and as there is no detachment of rubble as it is confined in the mesh, the system could be used in Category IV. This category allows the system to be suitable for use as façade cladding outside the reach of the ground level, not allowing its use on plinths, ground floors in front of public spaces and similar situations.
3.4. Discussion Overview
The following discussion overview presents a step-by-step and cross-sectional analysis of the results from a series of tests conducted on a full-scale prototype of a cable-suspended DSF. These tests were designed to evaluate the façade’s performance under different load conditions, including wind loads, seismic loads, and impact loads. The objective was to gain insights into the structural behaviour of this innovative façade system under realistic load scenarios, thereby contributing to the ongoing research in this field.
In the present research, in addition to the characterisation of individual components, experimental characterisation and testing of the construction system was conducted to verify its performance. A summary of the results of these tests is shown in
Table 2 below. A priori, tests of wind pressure and suction, impact, and seismic behaviour. Once the experimental data has been obtained, the process proceeds to a feedback and redesign of elements if necessary, following the scheme foreseen in the design and characterisation of individual components already described.
From the overall analysis of the results, it is determined that the use of flexible ceramic systems in DKF can be a suitable alternative to rigid ventilated façade solutions even under stressful wind, impact or seismic conditions that evaluate the stability of the constituent elements of the ceramic sheet. In the full-scale tests, the appropriate strength and stability of the metal components were assessed, and even though some of the ceramic tiles were damaged or broken, most of the tested prototype coped adequately with the test’s cycles. If the proposed system is compared with conventional ventilated façade solutions, it is easier, in this case, to adapt it to adverse conditions, especially under seismic and wind loads conditions. Furthermore, when a failure occurs, it is easy to replace the ceramic tiles due to system design and it implies less of a risk in case of detachment compared to conventional cladding panels.
4. Conclusions
The interaction between wind and seismic loads with permeable Double Skin Façades (DSF) can be particularly critical. This is especially true when different deformation ranges coexist in both façade sheets because one of them is a flexible constructive system. This paper seeks to bridge this research gap by presenting the findings of an experimental program specifically designed to evaluate the performance of such non-structural components under lateral loads. The paper, then, presents an evaluation of the behavior and stability of permeable, cable-supported DSF. The performance assessment was carried out using a comprehensive methodology that measured the individual capacities of connections, components, and materials. This was achieved through the application of both standardized and non-standardized testing procedures. The performance assessment was conducted following a five-step methodology: design of system components, analysis of regulatory requirements, definition of test plan, adaptation, and application of test procedures, and, finally, evaluation, validation and adaptation of system and individual components.
Key findings indicated that the connection mechanism between the cable, the restraint devices and their attachment to the building structure overcome highly demanding service stresses. Despite successfully passing most of the tests, based on the full-scale results, the type and diameter of the initially used stranded cables, as well as the cable lugs and cable-terminal joints, were redesigned and adjusted. Comparing the acquired results of the proposed DSF with other obtained from similar constructive solutions such as the one analyzed by Reyes et al. [
7], in the experimental wind assessment, whereas in the present case study the full-scale sample was subjected to a maximum pressure up to 3200 Pa obtaining a maximum relative displacement of 56,43 mm with 14,20 mm of permanent deformation, in the same test, Reyes et al. exposed the outer layer of their ventilated façade case study to a pressure of 1590 Pa obtaining a maximum mid-height relative displacement of 198 mm with 87 mm of permanent deformation. For both case studies, when exposed to wind loads, it was proved the high adaptability of flexible DSF systems and the progressive distention of the cables when the lateral load increased; nevertheless, only local damages was evidenced at the end of the tests. In the earthquake testing, the improved performance of the outer DSF sheet was demonstrated due to its flexibility when compared to the collapse of the rigid inner walls of the prototype. Similarly, in the impact testing, only when a higher load was applied, both in the hard body and soft body cases, was it possible to observe damage to the system components under test. All this leads one to consider the convenience of further developing flexible ventilated façade systems as suitable alternatives in the construction and refurbishment of buildings.
Author Contributions
Conceptualization, Pérez-Fenoy, Rivera-Gómez and Galán-Marín; methodology, Pérez-Fenoy, Rivera-Gómez and Galán-Marín; validation, Pérez-Fenoy, Rivera-Gómez and Galán-Marín; formal analysis, Pérez-Fenoy, Rivera-Gómez, Roa-Fernández and Galán-Marín; investigation, Pérez-Fenoy, Rivera-Gómez and Galán-Marín; resources, Pérez-Fenoy, Rivera-Gómez, Roa-Fernández and Galán-Marín; data curation, Pérez-Fenoy, Rivera-Gómez, Roa-Fernández and Galán-Marín; writing—original draft preparation, Pérez-Fenoy, Rivera-Gómez and Galán-Marín; writing—review and editing, Pérez-Fenoy, Rivera-Gómez, and Galán-Marín; supervision, Pérez-Fenoy, Rivera-Gómez and Galán-Marín; funding acquisition, Pérez-Fenoy, Rivera-Gómez and Galán-Marín. All authors have read and agreed to the published version of the manuscript.
Funding
This work has been supported by the European Regional Development Fund and CDTI, within the Operational Program for Intelligent Growth (ERDF) 2014-2020 and by the “European Union NextGenerationEU/PRTR”, project PROYEXCEL_00532 funded by Junta de Andalucía (Consejería de Transformación Económica, Industria, Conocimiento y Universidades) and grant US.22-07, funded by Junta de Andalucía (Consejería de Fomento, Articulación del Territorio y Vivienda).
Acknowledgments
The authors would like to thank to Cerámica Malpesa S.A. for the support shown during the execution of the prototypes and to The Eduardo Torroja Institute for Construction Sciences (IETcc) for the technical advice in carrying out the full-scale tests described in this paper.
Conflicts of Interest
The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.
Appendix A
This appendix is a section that contains details and data supplemental to the main text but nonetheless remain crucial to understanding and reproducing the research shown.
Table A1.
Earthquake testing: Loading protocol. Cycles and target displacements.
Table A1.
Earthquake testing: Loading protocol. Cycles and target displacements.
Cycle |
Target displacement (mm) |
Speed (mm/s) |
1 |
0,6200 |
0,05 |
2 |
1,9189 |
0,1 |
3 |
3,8383 |
4 |
5,7567 |
5 |
7,6756 |
0,3 |
6 |
11,5134 |
7 |
17,2000 |
0,6 |
8 |
25,9053 |
9 |
30,7026 |
10 |
46,0538 |
0,8 |
11 |
61,4051 |
12 |
76,7564 |
13 |
90,0000 |
14 |
100,0000 |
15 |
120,0000 |
Figure A1.
Earthquake testing: Loading protocol. Displacement at the head of the gantry (d) versus test execution time (t). Percentage of displacement in relation to the height of the panel (Drift (d/H'*100).
Figure A1.
Earthquake testing: Loading protocol. Displacement at the head of the gantry (d) versus test execution time (t). Percentage of displacement in relation to the height of the panel (Drift (d/H'*100).
Table A2.
Earthquake testing: Measuring sensors.
Table A2.
Earthquake testing: Measuring sensors.
Element |
Number |
Location |
Use |
Strain gage band |
37 |
10 on the outer leaf and 3 on the inner leaf of the pre-existing enclosure. 6 units at each of the 4 nodes of the portico. |
Masonry sheets deformations area |
Linear transducer
|
23 |
10 on the right pillar, 6 on the upper beam and 7 on the bases and anchor plates of the joints. |
Portal frame deformation area |
Accelerometer |
4 |
Depending on the test situation |
Vibration size |
Photographic equipment |
6 |
2 in front general view and a rear general view, and 4 in each quadrant of the sample. |
Performance recording during the test. |
Table A3.
Earthquake testing: Load cycles performed during the test.
Table A3.
Earthquake testing: Load cycles performed during the test.
Cycle |
Target displacement (mm) |
Achieved displacement (mm) |
Speed (mm/s) |
1 |
Noval |
0,6200 |
0,65 |
0,05 |
Reloading |
0,64 |
2 |
Noval |
1,9189 |
1,93 |
0,1 |
Reloading |
1,95 |
3 |
Noval |
3,8383 |
3,84 |
Reloading |
3,94 |
4 |
Noval |
5,7567 |
5,80 |
Reloading |
5,80 |
5 |
Noval |
7,6756 |
7,76 |
0,3 |
Reloading |
7,71 |
6 |
Noval |
11,5134 |
11,63 |
Reloading |
11,59 |
7 |
Noval |
17,2000 |
17,36 |
0,6 |
Reloading |
17,33 |
8 |
Noval |
25,9053 |
25,96 |
Reloading |
26,05 |
9 |
Noval |
30,7026 |
30,69 |
Reloading |
30,83 |
10 |
Noval |
46,0538 |
46,06 |
0,8 |
Reloading |
46,30 |
11 |
Noval |
61,4051 |
61,57 |
Reloading |
61,51 |
12 |
Noval |
76,7564 |
76,98 |
Reloading |
76,90 |
13 |
Noval |
90,0000 |
100,00 |
Reloading |
100,12 |
14 |
Noval |
100,0000 |
Stopped |
Reloading |
Stopped |
15 |
Noval |
120,0000 |
Stopped |
Reloading |
Stopped |
Table A4.
Impact testing: Use categories [43].
Table A4.
Impact testing: Use categories [43].
Test |
Use |
I |
A zone readily accessible at ground level to the public and vulnerable to hard body impacts but not subjected to abnormally rough use. (e.g.: Façade bases in buildings sited in public locations, such as squares, schoolyards, or parks. Cleaning gondolas may be used on the façade). |
II |
A zone liable to impacts from thrown or kicked objects, but in public locations where the height of the kit will limit the size of the impact; or at lower levels where access to the building is primarily to those with some incentive to exercise care (e.g.: Façade bases in buildings not sited in public locations (e.g. squares, schoolyards, parks) or upper façade levels in buildings sited in public locations that occasionally can be hit by a thrown object (e.g. ball, stone, etc.). Cleaning gondolas may be used on the façade). |
III |
A zone not likely to be damaged by normal impacts caused by people or by thrown or kicked objects (e.g.: Upper façade levels in buildings (not including base) not sited in public locations, that occasionally can be hit by a thrown object (e.g., ball, stone, etc.). Cleaning gondolas should not be used on the façade). |
IV |
A zone out of reach from ground level (e.g., high façade levels that cannot be hit by a thrown object. Cleaning gondolas should not be used on the façade). |
Table A5.
Impact testing: Hard and soft body impact tests [43,46].
Table A5.
Impact testing: Hard and soft body impact tests [43,46].
External impacts and assessment (In red values for replaceable products) |
|
|
|
Category IV |
Category III |
Category II |
Category I |
Hard body impact |
H1 |
Weight: 0,5 kg Impact: 1 J (height 0,20 m) 0,5 J (height 0,10m) No. impacts: 3 Position of impacts: three different locations |
No Pen2 No Per3
|
|
|
|
H2 |
Weight: 0,5 kg Impact: 3 J (height 0,61 m) 1 J (height 0,20 m) No. impacts: 3 Position of impacts: three different locations |
|
No Pen2 No Per3
|
No Det1
|
No Det1
|
H3 |
Weight: 1 kg Impact: 10 J (height 1,02 m) 3 J (height 0,31 m) No. impacts: 3 Position of impacts: three different locations |
|
|
No Pen2 No Per3 No Det1
|
No Det1
|
Soft body impact |
S1 |
Weight: 3 kg Impact: 10 J (height 0,34 m) 6 J (height 0,20 m) No. impacts: 3 Position of impacts: three different locations |
No Det1
|
No Det1
|
|
|
S2 |
Weight: 3 kg Impact: 60 J (height 2,04 m) 20 J (height 0,68 m) No. impacts: 3 Position of impacts: three different locations |
|
|
No Det1
|
No Det1
|
S3 |
Weight: 50 kg Impact: 300 J (height 0,61 m) 100 J (height 0,20 m) No. impacts: 1 Position of impacts: At least in the centre point of a cladding element |
|
|
No Det1
|
|
S4 |
Weight: 50 kg Impact: 400 J (height 0,82 m) 130 J (height 0,27 m) No. impacts: 1 Position of impacts: At least in the centre point of a cladding element |
|
|
|
No Det1
|
To have a magnitude baseline of the pressures reached during the test and their effects, these pressures have been translated into wind speeds (
Table A6) and the different speeds to which the façade elements have been subjected have been placed on the Beaufort Scale (
Table A7), used to measure the wind speed according to its effects observed on the earth's surface. As can be seen between the two tables, a pressure of 1800 Pa (≈199 km/h for an air density of 1.184 kg/m
3), a test step in which no defects occur in the façade elements, would be by far equivalent to a hurricane situation in which the complete stability of vehicles, houses, trees, or people is called into question.
Table A6.
Air pressure to air velocity.
Table A6.
Air pressure to air velocity.
Pa |
kN/m2
|
m/s |
km/h |
300 |
0,3 |
22,51 |
81 |
500 |
0,5 |
29,06 |
105 |
1000 |
1 |
41,10 |
148 |
1200 |
1,2 |
45,02 |
162 |
1400 |
1,4 |
48,63 |
175 |
1600 |
1,6 |
51,99 |
187 |
1800 |
1,8 |
55,14 |
199 |
2000 |
2 |
58,12 |
209 |
2200 |
2,2 |
60,96 |
219 |
Table A7.
Beaufort Wind Scale [49].
Table A7.
Beaufort Wind Scale [49].
Wind Force |
Description |
Wind Speed (km/h) |
Specifications |
0 |
Calm |
0-1 |
Smoke rises vertically. |
1 |
Light Air |
2-5 |
Direction shown by smoke drift but not by wind vanes. |
2 |
Light Breeze |
6-11 |
Wind felt on face; leaves rustle; wind vane moved by wind. |
3 |
Gentle Breeze |
12-19 |
Leaves and small twigs in constant motion; light flags extended. |
4 |
Moderate Breeze |
20-28 |
Raises dust and loose paper; small branches moved. |
5 |
Fresh Breeze |
29-38 |
Small trees in leaf begin to sway; crested wavelets form on inland waters. |
6 |
Strong Breeze |
38-49 |
Large branches in motion; whistling heard in telegraph wires; umbrellas used with difficulty. |
7 |
Near Gale |
50-61 |
Whole trees in motion; inconvenience felt when walking against the wind. |
8 |
Gale |
62-74 |
Twigs break off trees, generally impedes progress. |
9 |
Strong Gale |
75-88 |
Slight structural damage (chimney pots and slates removed). |
10 |
Storm |
89-102 |
Seldom experienced inland; trees uprooted; considerable structural damage. |
11 |
Violent Storm |
103-117 |
Very rarely experienced, accompanied by widespread damage. |
12 |
Hurricane |
>118 |
Devastation. |
References
- Tabadkani, A.; Roetzel, A.; Li, X.H.; Tsangrassoulis, A. Design approaches and typologies of adaptive facades: A review. Autom. Constr. 2021, 121, 103450. [Google Scholar] [CrossRef]
- Nawar, M.; Salim, H.; Lusk, B.; Kiger, S. Numerical simulation and verification of curtain wall systems under shock pressure. Pract. Period. Struct. Des. Constr. 1061. [Google Scholar]
- Renick, T.J.; Behr, R.A. Seismic performance of architectural glass in mid-rise curtain wall. J. Archit. Eng. 2002. [Google Scholar] [CrossRef]
- Villaverde, R. Seismic design of secondary structures: state of the art. J. Struct. Eng. 2002. [Google Scholar] [CrossRef]
- Behr, R.A. Design of architectural glazing to resist earthquakes. J. Archit. Eng. 2006. [Google Scholar] [CrossRef]
- Bedon, C.; Amadio, C. Numerical assessment of vibration control systems for multihazard design and mitigation of glass curtain walls. J. Build. Eng. 1016. [Google Scholar] [CrossRef]
- Reyes, J.C; Correal, J. F; Gonzales-Mancera, A; Echeverry, J.S; Gómez, I.D; Sandoval, J.D; Ángel, C.C. Experimental evaluation of permeable cable-supported façades subjected to wind and earthquake loads. Eng. Struct. 2020, 214, 110679. [Google Scholar] [CrossRef]
- Gerhardt, H.J.; Janser, F. Wind loads on wind permeable facades. J. Wind. Eng. Ind. Aerodyn. 1994. [Google Scholar] [CrossRef]
- Ancrossed, D.; Signelković, A.S.; Mujan, I.; Dakić, S. Experimental validation of a EnergyPlus model: application of a multi-storey naturally ventilated double skin façade. Energy Build. 2016. [Google Scholar] [CrossRef]
- Aparicio-Fernández, C.; Vivancos, J.L.; Ferrer-Gisbert, P.; Royo-Pastor, R. Energy performance of a ventilated façade by simulation with experimental validation. Appl. Therm. Eng. 2014. [Google Scholar] [CrossRef]
- Haase, M.; Marques da Silva, F.; Amato, A. Simulation of ventilated facades in hot and humid climates. Energy Build. 2009. [Google Scholar] [CrossRef]
- Liping, W.; Hien, W.N. The impacts of ventilation strategies and facade on indoor thermal environment for naturally ventilated residential buildings in Singapore. Build. Environ. 2007. [Google Scholar] [CrossRef]
- Liping, W.; Hien, W.N. The impacts of ventilation strategies and facade on indoor thermal environment for naturally ventilated residential buildings in Singapore. Build. Environ. 2007. [Google Scholar] [CrossRef]
- Bikas, D.; Tsikaloudakia, K.; Kontoleona, K.J.; Giarmaa, C.; Tsokaa, S.; Tsirigotia, D. Ventilated Facades: Requirements and Specifications Across Europe. Procedia Environ. Sci. 2017, 38, 148–154. [Google Scholar] [CrossRef]
- Hoffmann, S.; Lee, E.S.; McNeil, A.; Fernandes, L.; Vidanovic, D.; Thanachareonkit, A. Balancing daylight, glare, and energy-efficiency goals: An evaluation of exterior coplanar shading systems using complex fenestration modeling tools. Energy Build. 2016, 112, 279–298. [Google Scholar] [CrossRef]
- Mangkuto, R.A.; Rohmah, M.; Asri, A.D. Design optimisation for window size, orientation, and wall reflectance with regard to various daylight metrics and lighting energy demand: A case study of buildings in the tropics. Appl. Energy 2016, 164, 211–219. [Google Scholar] [CrossRef]
- Yun, G.; Yoon, K.C.; Kim, K.S. The influence of shading control strategies on the visual comfort and energy demand of office buildings. Energy Build. 2014, 84, 70–85. [Google Scholar] [CrossRef]
- Khoroshiltseva, M.; Slanzi, D.; Poli, I. A Pareto-based multi-objective optimization algorithm to design energy-efficient shading devices. Appl. Energy 2016, 184, 1400–1410. [Google Scholar] [CrossRef]
- Ascione, F.; Bianco, N.; Mauro, G.M.; Vanoli, G.P. A new comprehensive framework for the multi-objective optimization of building energy design: Harlequin. Appl. Energy 2019, 241, 331–361. [Google Scholar] [CrossRef]
- Lops, C.; Germano, N.; Matera, S.; D’Alessandro, V.; Montelpare, S. CFD modelling of naturally ventilated Double Skin Façades: Comparisons among 2D and 3D models. Tec. Ital. Ital. J. Eng. Sci. 2021, 65, 330–336. [Google Scholar] [CrossRef]
- İpek, S.; Güneyisi, E.M. Nonlinear finite element analysis of double skin composite columns subjected to axial loading. Archiv. Civ. Mech. Eng. 2020, 20, 9. [Google Scholar] [CrossRef]
- Catto Lucchino, E.; Goia, F.; Lobaccaro, G.; et al. Modelling of double skin facades in whole-building energy simulation tools: A review of current practices and possibilities for future developments. Build. Simul. 2019, 12, 3–27. [Google Scholar] [CrossRef]
- European-Spanish harmonised Product standards and requirements. UNE-EN 14411:2016. Ceramic tiles. Definitions, classification, characteristics, assessment, and verification of performance consistency and marking. 2016.
- Spanish Standard. AENOR. Asociación Española de Normalización y Certificación. RP 34.14 Revisión 7. Reglamento Particular de la Marca AENOR para piezas de arcilla cocida P para fábricas protegidas. 2017.
- Spanish Standard. AENOR. Asociación Española de Normalización y Certificación. RP 34.01 Revisión 20. Reglamento Particular de la Marca AENOR para piezas de arcilla cocida U para fábricas de albañilería no protegida. 2017.
- European-Spanish harmonised Product standards and requirements. UNE 67039:1993 EX. Fired clay ceramic products. Determination of calcareous inclusions. 1993. 1993.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-16:2011. Test methods for masonry units. Part 16: Determination of dimensions. 2011.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-20:2001+A1:2006. Test methods for masonry units - Part 20: Determination of flatness of faces of masonry units. 2006.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-1:2011+A1:2016. Test methods for masonry units. Part 1: Determination of compressive strength. 2016.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-13. Test methods for masonry units. Determination of dry density and dry bulk density of masonry units (except natural stone). 2001.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-3:1999. Test methods for masonry units. Part 3: Determination of net volume and void ratio by hydrostatic weighing of baked clay masonry units. 1999.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-21:2011. Test methods for masonry units - Part 21: Determination of water absorption of baked clay and sand-lime masonry units by cold water absorption. 2011.
- European-Spanish harmonised Product standards and requirements. UNE-EN ISO 10545-4:2015. Ceramic tiles. Part 4: Determination of flexural strength and breaking strength. (ISO 10545-4:2014) 2015.
- European-Spanish harmonised Product standards and requirements. UNE 67029:1995 EX. Fired clay ceramic bricks. Efflorescence test. 1995. 1995.
- European-Spanish harmonised Product standards and requirements. UNE 67028:1997 EX. Fired clay ceramic bricks. Freezing test. 1997. 1997.
- European-Spanish harmonised Product standards and requirements. UNE-EN 772-5:2016. Test methods for masonry pieces. Part 5: Determination of the content of active soluble salts in fired clay masonry units. 2016.
- European-Spanish harmonised Product standards and requirements. UNE-EN ISO 6892-1:2017. Metallic materials. Tensile test. Part 1: Test method at room temperature. 2017.
- EOTA European Organisation for Technical Approvals. ETAG 034. Guideline for European Technical Approval of Kits for External Wall Claddings. Part I: Ventilated cladding kits comprising cladding components and associated fixings. 2012.
- EOTA European Organisation for Technical Approvals. ETAG 034. Guideline for European Technical Approval of Kits for External Wall Claddings. Part II: Cladding kits comprising cladding components, associated fixings, subframe and possible insulation layer. 2012.
- Pallarés, F.J; Pallarés, L. Experimental study on the response of seismically isolated masonry infilled steel frames during the initial stages of a seismic movement. Eng. Struct. 2016, 129, 44–53. [Google Scholar] [CrossRef]
- FEMA. Federal Emergency Management Agency. FEMA 461. Interim testing protocols for determining the seismic performance characteristics of structural and nonstructural components. 2007. 2007.
- Ministerio de Transportes, Movilidad y Agenda Urbana. Código Técnico de la Edificación. Documento Básico. Seguridad Estructural. Acciones en la edificación (CTE-DB-SE-AE). 2009.
- EOTA European Organization for Technical Approvals. EAD 090062-00-0404. Kits for external wall claddings mechanically fixed. 2018.
- Ministerio de Transportes, Movilidad y Agenda Urbana. Norma de Construcción Sismorresistente. Parte General y Edificación (NCSE-02). 2002.
- Rivera-Gómez, C.; Pérez-Fenoy, J.; Entrenas-Angulo, J.A.; López-Aguilar, M.; Galán-Marín, C. Performance validation and manufacture feasibility for an advanced constructive system considering facilities integration. J. Build. Eng. 2020, 29, 101127. [Google Scholar] [CrossRef]
- ITeC Instituto de Tecnología de la Construcción de Cataluña. Criterios ITeC: Resistencia frente a impactos en revestimientos de fachada. 2020.
- Ksschulten. Available online: https://www.ksschulten.com/en/products/test-engineering/346-ks-test-engineering-worldwide.html (accessed on 5 September 2023).
- IVE. Instituto Valenciano de la Edificación. Catálogo de tipología edificatoria residencial. Ámbito: España; 1ª ed.; Generalitat Valenciana: Valencia, España. 2016; 12–61.
- Beaufort Wind Scale. Royal Meteorological Society. Available online: https://www.rmets.org/metmatters/beaufort-wind-scale (accessed on 5 September 2023).
Figure 1.
Methodology overview.
Figure 1.
Methodology overview.
Figure 7.
Arrangement of the linear measurement transducers on the sample under test: (a) Reference in red for execution of configurations 1 and 2; references in blue for execution of configuration 3. All dimensions in millimetres.
Figure 7.
Arrangement of the linear measurement transducers on the sample under test: (a) Reference in red for execution of configurations 1 and 2; references in blue for execution of configuration 3. All dimensions in millimetres.
Figure 8.
Wind pressure test results: (a) Displacements obtained in each of the configurations at all indicated load steps; (b) Residual deformation value after load application has stopped for each configuration.
Figure 8.
Wind pressure test results: (a) Displacements obtained in each of the configurations at all indicated load steps; (b) Residual deformation value after load application has stopped for each configuration.
Figure 9.
Deformation about the horizontal for each configuration. Maximum values.
Figure 9.
Deformation about the horizontal for each configuration. Maximum values.
Figure 10.
Deformation about the vertical for each configuration. Maximum values.
Figure 10.
Deformation about the vertical for each configuration. Maximum values.
Figure 11.
(a) Deformation of the sample plane during the execution of test 3 under 3200 Pa pressure; (b) Damaged ceramic pieces at the end of the test.
Figure 11.
(a) Deformation of the sample plane during the execution of test 3 under 3200 Pa pressure; (b) Damaged ceramic pieces at the end of the test.
Figure 12.
Comparison of the central cable of the theoretical model with the experimental model. Configuration 2 (2 retainers/m2). Comparison between the experimental deformation (solid lines) and the theoretical deformation of the cable (dashed lines), considering a free span of L = 1 m.
Figure 12.
Comparison of the central cable of the theoretical model with the experimental model. Configuration 2 (2 retainers/m2). Comparison between the experimental deformation (solid lines) and the theoretical deformation of the cable (dashed lines), considering a free span of L = 1 m.
Figure 13.
Comparison of the theoretical model central cable on the experimental model after adjusting the theoretical model. Configuration 2 (2 retainers/m2). Comparison between the experimental deformation (solid lines) and the theoretical deformation of the cable (dashed lines), considering a clear span of L = 1 m.
Figure 13.
Comparison of the theoretical model central cable on the experimental model after adjusting the theoretical model. Configuration 2 (2 retainers/m2). Comparison between the experimental deformation (solid lines) and the theoretical deformation of the cable (dashed lines), considering a clear span of L = 1 m.
Figure 14.
Pre-existing cladding: (a) Outer leaf of facing brick; (b) Inner leaf composed of a double hollow brick lining.
Figure 14.
Pre-existing cladding: (a) Outer leaf of facing brick; (b) Inner leaf composed of a double hollow brick lining.
Figure 15.
(a). Elevation and exploded view of reinforcement for the reinforced concrete portal frame. Dimensions in mm. (b). Ventilated façade leaf built over the pre-existing frame and cladding.
Figure 15.
(a). Elevation and exploded view of reinforcement for the reinforced concrete portal frame. Dimensions in mm. (b). Ventilated façade leaf built over the pre-existing frame and cladding.
Figure 16.
Cycles during test: (a) Load-time; (b) Displacement-time; and (c) Load-displacement.
Figure 16.
Cycles during test: (a) Load-time; (b) Displacement-time; and (c) Load-displacement.
Figure 17.
Damages in the pre-existing cladding at the end of the test: (a) Front view of the sample. State of the facing brick sheet after removing the ventilated façade sheet. And (b) Rear view of the sample. State of the interior facing brick sheet.
Figure 17.
Damages in the pre-existing cladding at the end of the test: (a) Front view of the sample. State of the facing brick sheet after removing the ventilated façade sheet. And (b) Rear view of the sample. State of the interior facing brick sheet.
Figure 18.
Sample front view. Detail of lesions in ceramic tiles on the ventilated façade leaf.
Figure 18.
Sample front view. Detail of lesions in ceramic tiles on the ventilated façade leaf.
Figure 19.
Sample front view, non-ceramic elements at the end of the test: (a) Detail of the state of the wire ropes. And (b) Detail of the state of the wind restraint device.
Figure 19.
Sample front view, non-ceramic elements at the end of the test: (a) Detail of the state of the wire ropes. And (b) Detail of the state of the wind restraint device.
Figure 20.
Concrete frame deformation in the last cycle when the maximum head displacement is reached.
Figure 20.
Concrete frame deformation in the last cycle when the maximum head displacement is reached.
Figure 21.
Devices used for impact tests: (a) 0.5 kg and (b) 1 kg steel ball as hard bodies. And (c) 3 kg and (d) 50 kg bags as soft bodies.
Figure 21.
Devices used for impact tests: (a) 0.5 kg and (b) 1 kg steel ball as hard bodies. And (c) 3 kg and (d) 50 kg bags as soft bodies.
Figure 22.
Position criteria for hard body (blue H-marks) and soft body (magenta S-marks) impacts on geometrical definition of the test specimen.
Figure 22.
Position criteria for hard body (blue H-marks) and soft body (magenta S-marks) impacts on geometrical definition of the test specimen.
Figure 23.
Procedure for the use of impact bodies. 1. Determine point of impact. Green point; 2. Dimension H. Height of fall according to body type and the impact energy in joules (J) according to ETAG 034 and EOTA Technical Report TR001; 3. Anchor point for the impact pendulum determined by 1,75*H; 4a. Height from the anchor point to the ground; 4b. Sample separation coincident with the radius of the impact ball; 5. Angular range between vertical and impact body actuator; 6. Impact body actuator.
Figure 23.
Procedure for the use of impact bodies. 1. Determine point of impact. Green point; 2. Dimension H. Height of fall according to body type and the impact energy in joules (J) according to ETAG 034 and EOTA Technical Report TR001; 3. Anchor point for the impact pendulum determined by 1,75*H; 4a. Height from the anchor point to the ground; 4b. Sample separation coincident with the radius of the impact ball; 5. Angular range between vertical and impact body actuator; 6. Impact body actuator.
Figure 24.
Hard body (HB) and Soft body (SB) impact tests results: Applying 0,5 Kg: (a) HB 1 J energy and (b) HB 3 J energy. Applying 3 kg: (c) SB 10 J of energy and (b) SB 60 J of energy.
Figure 24.
Hard body (HB) and Soft body (SB) impact tests results: Applying 0,5 Kg: (a) HB 1 J energy and (b) HB 3 J energy. Applying 3 kg: (c) SB 10 J of energy and (b) SB 60 J of energy.
Figure 25.
Position of the hard body (H1, H1R, H2 and H2R) and soft body (S1 and S2) impacts performed in the test.
Figure 25.
Position of the hard body (H1, H1R, H2 and H2R) and soft body (S1 and S2) impacts performed in the test.
Table 1.
Characterization of DSF system ceramic components.
Table 1.
Characterization of DSF system ceramic components.
Test |
Samples |
Standard |
Results |
Description |
- |
UNE-EN 14411:2016 [23] |
Extruded ceramic pieces |
Aspect and structure |
6 |
R.P. 34.14 - Rev. 7 [24] R.P. 34.01 - Rev. 20 [25] |
Undamaged |
Calcareous inclusions |
6 |
UNE 67039:1993 EX [26] |
Undamaged |
Mass |
6 |
R.P. 34.14 - Rev. 7 [24] R.P.34.01 - Rev. 20 [25] |
525 ± 5 g |
Dimensions |
10 |
UNE-EN 772-16:2011 [27] |
Thickness |
Length |
Height |
24 ± 2 mm |
237 ± 2 mm |
43+3 ± 0,5 mm |
Flatness of faces |
6 |
UNE-EN 772-20:2001 - A1/2006 [28] |
Face type |
Diagonal medium |
Deviation medium |
Deviation maximum |
Bed |
237 ± 2 |
0 ± 0,5 |
0 ± 0,5 |
Stretcher |
242 ± 2 |
1,1 ± 0,5 |
1,6 ± 0,5 |
Header |
49 ± 2 |
0,3 ± 0,5 |
0,3 ± 0,5 |
Parallelism of the beds |
3 |
UNE-EN 772-16:2011 [27] |
0,2 ± 0,2 mm |
Compression strength |
10 |
UNE-EN 772-1:2011/A1:2016 [29] |
≥ 20 (40 in pieces type klinker) N/mm2
|
Absolute density |
10 |
UNE-EN 772-13:2001 [30] |
2150 ± 100 kg/m3
|
Dry bulk density |
1970 ± 80 kg/m3
|
Net volume |
10 |
UNE-EN 772-3:1999 [31] |
250 ± 10 cm3
|
Percentage of voids |
10 |
≤ 8 % |
Water absorption |
10 |
UNE-EN 772-21:2011 [32] |
≤ 1 % |
Flexural strength and breaking load |
|
UNE-EN-ISO 10545-4:2012 [33] |
Position |
Breaking load |
Breaking strength |
Flexural Strength |
10 |
Position A
|
2369 N |
18158 N |
12,5 N/mm2
|
|
10 |
Position B
|
413 N |
1595 N |
4,3 N/mm2
|
|
10 |
Position C |
5708 N |
14349 N |
9,8 N/mm2
|
|
Efflorescence |
6 |
UNE 67029:1995 EX [34] |
Not effloresced |
Heladicity |
6 |
UNE 67028:1997 EX [35] |
Non-frosting pieces |
Soluble salt content |
10 |
UNE-EN 772-5:2016 [36] |
Na+ + K+ (%) |
0,01 % |
Mg2+ (%) |
0,01 % |
Table 2.
Characterization of component and system performance.
Table 2.
Characterization of component and system performance.
Test |
Samples |
Standard |
Results |
Breaking strain stranded cable
|
6 |
UNE-EN ISO 6892-1:2017 [37] |
2807,56 N |
Supporting set strength to vertical force |
|
Tests based on ETAG 034 [38,39] |
Displacement force |
Ultimate strength |
|
para 1 mm (Rc1mm)1 |
para 3 mm (Rc3mm) 1 |
Rcu1 |
5 |
1,79 kN |
4,71 kN |
4,67 kN |
Supporting set strength to horizontal force |
|
|
Residual deformation 1 mm |
Ultimate strength |
|
|
Rc1mm1 |
Rcu1 |
5 |
Suction |
7,76 kN |
7,57 kN |
5 |
Pressure |
7,30 kN2
|
7,30 kN |
Cable and the tensioner strength. Pure traction
|
|
|
Elastic limit |
Maximum strength |
|
|
Rcu1
|
Rcu1
|
5 |
Normal |
1789,16 N |
2104,60 N |
5 |
Fatigued |
1783,45 N |
1923,80 N |
|
Ratio |
99,7 % |
91,4 % |
Wind-holding strength unit to horizontal suction force |
|
|
Maximum strength |
|
|
Rcu1 |
5 |
Normal |
2680,70 N |
5 |
Fatigued |
2818,60 N |
|
Ratio |
100 % |
Flange strength of parts |
|
|
Flange breaking strength |
|
|
Rcu1 |
5 |
Central |
553,90 N |
5 |
Extreme |
382,80 N |
Hard and soft body impacts. Complete set up |
1 |
|
Classification |
Soft body |
S1 |
Hard body |
H2 |
Classification |
Category IV |
Wind pressure and suction. Complete set-up |
1 |
Retainers /m2 |
MaximumQ
|
Displacement |
Under max Q |
After 1 min recovery |
2 |
2400 Pa |
21,90 mm |
3,10 mm |
1 |
3200 Pa |
56,43 mm |
14,20 mm (Para 3000 Pa)
|
Earthquake resistance |
1 |
Test based on [40,41] |
Small cracks in the ceramic pieces, without detachment of rubble. The test is stopped due to collapse of the inner and intermediate leaves belonging to the traditional test leaf. |
|
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).