1. Introduction
Inerter-based dampers have recently seen tremendous growth in popularity for controlling structural vibration [
1]. Inerter is used for the mass enhancement effects, and its resisting force is predicted to be proportional to the relative acceleration between ends [
2]. A tuned mass damper-inerter (TMDI) simulates a conventional tuned mass damper (TMD) with an inerter. Additionally, it is referred to as a tuned inerter damper (TID) when the TMD mass is replaced with the inerter. The performance of base-isolated structures with TMDI fixed to the isolation floor under both real and stochastic earthquake excitation was examined [
3,
4,
5,
6,
7,
8,
9,
10,
11,
12,
13]. It was demonstrated that the TMDI reduces the response of base-isolated structures equipped with linear as well as non-linear isolators. Enhanced performance of the optimal TMDI was further observed when it was placed on the upper floors of the isolated structure or used in tandem [
14,
15]. Recently, it has also been demonstrated experimentally that it is possible to achieve reasonable results in the response of base-isolated structures augmented with TMDI by using a simplified linear dissipative model instead of a nonlinear model with friction and gear backlash [
16,
17]. The efficiency and optimum TID parameters for the base-isolated structure when considering the stochastic model of earthquake excitation are also illustrated [
18,
19,
20,
21,
22,
23]. To reduce the seismic response and vibration isolation in the base-isolated structures, a geometrically nonlinear TID arrangement is also being investigated for multidirectional isolation [
24]. The use of multiple TMD to control the seismic response of base-isolated buildings has recently been studied [
25,
26]. Another application of the inerter in seismic base isolation was the supplemental fluid inerter damper (FID) and electromagnetic inertial mass damper (EIMD). The performance of the base-isolated structures with FID has been investigated by various researchers and has shown that there are benefits in seismic response control [
27,
28,
29,
30,
31,
32,
33,
34]. Recently, the dynamic behaviour of EIMD and optimal parameters for reducing the structural response of base-isolated structures were also demonstrated [
35,
36]. The review above suggests that the researchers are very interested in using inerter-based supplemental devices for base-isolated structures.
The period of base-isolated structures is usually quite long, and the tuning effects of TMDI, TID, or TMD may not be achieved during the strong motion duration of the earthquake excitation. However, there is still a reduction in the response of the isolated structure, which is primarily due to the added damping and stiffness (ADAS) of the above devices and not because of the tuning effects [
37]. The tuned damper-type devices are relatively less effective for the system with higher damping than the corresponding systems with lower damping [
38]. It implies that for base-isolated buildings generally equipped with heavy damping, the supplemental tuned mass-type damper devices may not be very effective. Further, in the FID and EIMD, the inerter works in tandem with the fluid damper (FD) and electromagnetic damper (ED), and it's unclear whether the inerter or the FD and ED provide beneficial effects in response reduction. It may be possible that a single FD or ED can achieve similar or even better beneficial effects. As a result, it will be interesting to investigate the controlling effects of the inerter by examining the seismic response of base-isolated structures with FID or EIMD. This is proposed to be achieved by comparing the response of isolated structures with FID or EIMD with the corresponding response without inerter in the FID or EIMD devices.
Herein, the response of the base-isolated structures with supplemental optimal TMDI and FID is investigated for the tuning effects of TMDI and the role of inerter in FID. The specific objectives of the study are summarized to (i) investigate the tuning effects of TMDI in controlling the seismic response of the base-isolated structure equipped with TMDI, (ii) compare the response of base-isolated structures with TMDI to the corresponding response with ADAS device, (iii) understand the role of inerter in FID for seismic response control of base-isolated structure by comparing the corresponding response with FD, and (iv) to study the comparative performance of TMDI, ADAS, FID, and FD devices for flexible multi-story base-isolated structures subjected to real earthquakes.
3. Rigid Base-Isolated Structure with FID and FD
Figure 5a depicts a schematic diagram of FID installed in a rigid model of the base-isolated structure. The two terminals, represented by 1 and 2 on the FID, are coupled to the ends depicted in
Figure 1a of the base-isolated structure model. An FID typically consists of a piston and cylinder that force the fluid through a helical tube that is encircled by the cylinder. The hydraulic cylinder and the piston rod are the two terminals of the FID. The fluid flow through an external helical channel produces rotational inertia to compensate for the pressure loss [
42,
43,
44]. The FID's resisting force depends on the friction, oil density, and viscosity of the fluid. The FID is modelled as a linear inerter in parallel with a linear [
27,
28,
29,
32,
33] and a non-linear [
30,
31] dashpot for studying the seismic response of the base-isolated structures. For simplicity, the FID is modelled in the present study as a linear inerter (i.e., with an inertance coefficient as
b) in parallel with a linear viscous FD (i.e., with a damping coefficient of
cf). It is worth noting that this FID modelling is identical to the EIMD modelling described in the References [
35,
36].
The FID is defined by two parameters, β and ξ
f, which are both defined as:
Consider the rigid superstructure model of the base-isolated structure (refer to
Figure 1a) with supplemental FID. The governing equation of motion of a base-isolated structure with FID under earthquake excitation is expressed as
Dividing equation (11) by (
m+
b) and substituting
, the equation of motion reduces to
The above indicates that FID elongates the vibration period and decreases the total damping ratio (i.e., ) of the base-isolated structure. It also suppresses the level of earthquake shaking (as the denominator on the right-hand side is always larger than unity).
Let the rigid superstructure model of the base-isolated structure with FID be subjected to white-noise earthquake acceleration with PSDF as
S0. The mean square displacement of the isolated structure with FID will be [
45]
The above equation indicates that for broadband excitation, the displacement variance of the base-isolated structure is not influenced by the inertance of the FID. The reduction in displacement is primarily happening due to the added damping of the FID. Since the inerter of the FID does not influence the response of the isolated structures under broad band-excitation, it is therefore proposed that the corresponding FD only be added parallel to the isolation system (refer to
Figure 5b).
The absolute acceleration,
of the isolated structural mass with FID, is expressed as
Interestingly, two terms i.e., and are added to the absolute acceleration of the mass compared to the conventional isolation system, and it will be interesting to see their effects.
When subjected to the harmonic earthquake acceleration as
, the steady-state absolute acceleration,
is expressed as
where
is the FRF of the response
.
In
Figure 6, the variation of the FRF of the absolute acceleration of the mass of the isolated structure with FID is plotted. The FRF with β = 0 corresponds to the structure without FID. Because of the added supplement inertial mass by the FID, the resonating frequency decreases as the inertance ratio increases. The peak values of absolute acceleration also decrease with the increase of the β. However, for higher frequencies, the amplitude of absolute acceleration increases with the β and remains constant throughout. This implies that FID will transmit earthquake vibrations into the base-isolated structures associated with the higher frequencies. This can be detrimental to the sensitive high-frequency equipment or secondary system installed in the isolated structure. It is also to be noted that the mean square absolute acceleration of the isolated structure with FID,
when subjected to white-noise earthquake excitation.
5. Flexible Isolated Structure Under Real Earthquakes
An earlier study attempted the response of a rigid base-isolated structure with the optimum TMDI, ADAS, FID, and FD under stationary earthquake excitation. However, the behaviour of these devices under real earthquake excitation and when the isolated superstructure is assumed to be flexible will be interesting to explore. This will provide insight into the tuning behaviour and the frequency contents of the superstructure acceleration of the isolated structure with TMDI and FID.
Figure 8a depicts a typical five-story linear shear-type building equipped with supplementary TMDI, ADAS, FID, and FD devices in addition to a base isolation system. The base mass and the
ith floor mass are represented by
and
, respectively.
stands for the
ith floor's stiffness. The lead-rubber bearing (LRB) system is selected as an isolation device. Hysteretic damping is additionally produced by the lead core of the LRB through yielding, which dissipates the seismic energy input.
Figure 8b illustrates the simple bi-linear force-deformation behaviour of the LRB. The three variables
Fy,
kb, and
q, which stand for yield force, post-yield stiffness, and yield displacement, respectively, define the LRB's bi-linear characteristics. For the selected base-isolated structure with supplemental TMDI, ADAS, FID, and FD, the governing equations of motion are
where
M = mass matrix;
C = damping matrix;
K = stiffness matrix;
x(
t) = vector of horizontal displacements (relative to the ground) of each mass at time
t;
Di = location vector for the bi-linear restoring force of the LRB;
Fi(
t) = bi-linear restoring force of the LRB;
Ds = location matrix for the vector of control forces
Fs(
t) produced by the supplemental devices TMDI, ADAS, FID, and FD;
E = vector containing the vibrating masses; and
= earthquake acceleration specified by a time history.
A five-story building with linear inter-story stiffness and viscous damping is selected for the present study, and its parameters are taken from Kelly [
48]. All floors and base raft locations in the selected superstructure account for the same mass implying
mb =
mi (
i=1 to 5). The inter-story stiffness of various floors is taken as
k1,
k2,
k3,
k4, and
k5, which correspond to, respectively, 15
k, 14
k, 12
k, 9
k, and 5
k. The chosen value for
k results in a fundamental period of 0.4 seconds for the fixed base-superstructure. The superstructure with a fixed base has five natural frequencies that are measured in rad/sec and are 15.71, 38.48, 60.84, 83.12, and 105.37. Assuming that all vibrational modes have a modal damping ratio of 0.02, the superstructure's damping matrix is developed. The parameters
Tb and ξ
b (see equation (1)) are used to calculate the post-yield stiffness and damping of the LRB while considering the flexible base-isolated structure's total mass,
M (i.e.,
). The isolation damping ratio is selected as 10 percent. The yield strength of the LRB is selected as 0.05
W (i.e.,
W=
Mg represents the total weight of the base-isolated structure) and yield displacement as 0.025m. The normalized inertance, β of the supplemental devices is calculated by considering the total mass,
M. The auxiliary stiffness and damping of the optimal TMDI (for the specified value of
Tb and
) are selected corresponding to which minimizes the
of a rigid-base isolated structure under white-noise earthquake excitation using equations (8) and (9). The viscous damping of FID is defined by
using equation (10) and considering the total mass of the isolated structure, and taken as
=β/2. The seismic response of the isolated building with supplemental TMDI, ADAS, FID, and FD devices is evaluated numerically by solving the governing equations of motion using the step-by-step method [
49].
Three real earthquake motions, namely the north-south component of El-Centro, 1940 earthquake, N00E component of the 1989 Loma Prieta earthquake (measured at Los Gatos Presentation Centre), and 270 component of the 1992 Landers earthquake (measured at Lucerne Valley), are selected. The peak ground acceleration (PGA) of El-Centro, Loma Prieta, and Landers earthquake motions are 0.34g, 0.57g, and 0.73g, respectively. The response quantities of interest are the top floor absolute acceleration (), relative base displacement (xb), force in the isolation system (Fis), force in the supplemental device (Fsup), and total base shear (F). The selected force quantities are normalized with W.
The time variation of the top floor absolute acceleration, relative base displacement, the force in the isolation system, the force in the supplemental device, and total base shear are shown in
Figure 9. The responses are shown for the Loma Prieta, 1989 earthquake and compared with the corresponding response of isolated structures without supplemental devices (referred to as BIS). The figure indicates that the peak value of the top floor acceleration for BIS+TMDI, BIS+ADAS, and BIS+FD is the same as that of BIS, implying that these supplemental devices are not much altering the top floor acceleration. However, there is an almost 3.61 times increase in the peak top floor acceleration of the isolated structure with FID compared to the corresponding peak acceleration of BIS. This is unacceptable as the FID defeats the primary purpose of seismic isolation by increasing the structural acceleration. It was also noted that the base-isolated structure with FID's absolute acceleration contains high-frequency components, which could be harmful to equipment or a secondary system that is sensitive to high-frequency vibrations. There is a reduction in base displacement by all the supplemental devices. It was observed to decrease by 23.8 to 32.8 percent compared to the corresponding BIS. The base displacement of isolated structures with ADAS is less than the corresponding TMDI. This is interesting and primarily happens because the peak base displacement occurs in the large initial cycles of the response. By that time, the TMDI is not adequately tuned to dissipate the input seismic energy. However, the TMDI is more effective in reducing the subsequent peak response in comparison to the ADAS. The variation of force in the isolation system is similar to that of the isolator displacement for all supplemental devices. The peak value of the force in the supplemental devices for the isolated structure with FID is almost 3 to 4 times that of other devices. The peak total base shear is reduced for isolated structures with TMDI, ADAS, and FD and immensely increased for the FID compared to the corresponding total base shear of the BIS.
The effects of the β on the peak top floor absolute acceleration, relative base displacement, the force in the isolation system, the force in the supplemental device, and the total base shear of the base-isolated structure with different supplemental devices and earthquakes are shown in
Figure 10. The figure indicates that the peak top floor acceleration is not very sensitive to β and quite comparable to the base-isolated structures with supplemental TMDI, ADAS, and FD. However, the peak top floor acceleration increases with β for the isolated structure with supplemental FID. This can be explained with the help of
Figure 6, which shows that the grounded inerter connected to the base mass will directly transmit the vibration (i.e., accelerations) associated with high-frequency amplitudes in the earthquake ground motion. This confirms that the inerter in the FID has detrimental effects as a supplemental device to the isolation system, increasing the structural accelerations. The peak base displacement of the base-isolated structure with supplemental devices decreases with the increase of β. A comparison of the peak base displacement of the base-isolated structures with TMDI and the corresponding ADAS indicates a greater reduction in the base displacement by ADAS compared to TMDI.
Further, there is a greater reduction in base displacement for the isolated structures with FID than with FD. The variation of peak force in the isolation system has a similar trend to base displacement. The peak force in the supplemental devices increases with the increase in β. However, the force in the FID is substantially higher in comparison to the force of other supplemental devices. The peak total base shear of isolated structures with TMDI, ADAS, and FD is not very sensitive to the β but it increases for the FID. Thus, it can be concluded that the inerter in the FID increases the structural acceleration as well as the total base shear.
The effects of β on the peak top floor absolute acceleration, relative base displacement, the force in the isolation system, the force in the supplemental device, and the total base shear of the base-isolated structures with
Tb = 4 sec for different earthquakes are shown in
Figure 11. The trends of the results in
Figure 11 are similar to those observed in
Figure 10 for considering
Tb = 3 sec.
Based on the discussion of the presented results, it can be concluded that there is a greater or comparable reduction in the base displacement by corresponding ADAS in comparison to the optimal TMDI. Further, an inerter of the FID attached to the ground and an isolated structure have detrimental effects on seismic isolation by transmitting the vibrations associated with high-frequency accelerations and increasing the base shear. The study's overall conclusion is that inerter-based supplemental devices such as TMDI and FID may not be very effective for the base-isolated structures to warrant their practical application. On the other hand, a pair of inerters with a clutching effect might be able to significantly reduce the displacement in the base-isolated structure's isolation system [
50,
51,
52,
53]. Also, the performance of the inerter-based dampers in conjunction with negative stiffness devices was somewhat encouraging for the base-isolated structures [
54,
55]. The current study is primarily concerned with the inerter's function in the recently investigated supplemental dampers for base-isolated structures. However, it is strongly recommended to compare their performance with the widely researched dampers, such as magnetorheological dampers, negative stiffness dampers, semi-active variable friction and stiffness devices, etc. It is also recommended that the findings of the present study be experimentally validated.