1. Introduction
Sandwich panels crafted with concrete skins and insulating cores are a competitive solution for building structural components with energy efficient added value, see a review in Oliveria et al. [
1]. The concern about climate changes and sustainable solutions drive research towards more green and bio-based engineering sandwich technologies according Oliveira et. al. [
2]. In the present work a solution based on vegetal FRCM and polystyrene core, serve as a lightweight construction solution with noteworthy insulating properties for building enclosures. The mechanical properties of these panels depend significantly on the composite action between materials. Adequate material connection is crucial, as insufficient bonding may result in problematic stress distribution within the panel, potentially causing detachment failure or a substantial decrease in mechanical strength.
In this order, different authors presented previous studies like Cox et al. [
3] develop a composite shear connectors system of glass fiber reinforced polymer (GFRP) used to transfer interface shear forces in a precast concrete sandwich panel. The study developed push-off, pullout, and flexural tests, to evaluate the structural performance of the shear connectors, and the effect of bond between concrete and insulation with a push-off tests. The results showed satisfactory performance with a lower bound of 90% composite action for specimens with 100mm thick insulation wythe and full composite action for most panels with 50mm thick insulation. Other study by Portal et al. [
4] presented experimental and numerical methods to analyzed the structural behaviour related to a sandwich panel with a glass fibre reinforced polymer (GFRP) plate connection system, where a double shear tests were conducted on sandwich specimens to characterize the available shear capacity provided by the connectors and panel configuration. The authors conclude that for well-balanced composite action is necessary use least material in the plate connectors, and increased bending capacity of the outer panel to avoid a significant drop of the load after the peak load. At the same line, Hulin et al. [
5] presents an experimental campaign at elevated temperatures for panels stiffened by structural ribs, insulation layers, and steel shear connectors. The results highlighted insulation shear failure from differential thermal expansion at the interface with concrete, where the shear connectors induced to stress concentrations leading to local failure. A study presented by Tomlinson et al. [
6] carry out push-through tests on precast concrete insulated sandwich panel using combined angled and horizontal connectors, where basalt fibre reinforced polymer and steel connectors were used. This study evaluated various inclination angles and diameters of connectors, orientation of the diagonal connector relative to loading, and panels with or without an active foam to concrete bond. The results show that steel connectors failed by yielding in tension and inelastic buckling in compression. In the case of the larger-diameter basalt-FRP connectors pulled out under tension and crushed in compression, and smaller-diameter basalt-FRP connectors ruptured in tension and buckled in compression. Also, it is demonstrated that the strength and stiffness improved with the connector angle and diameter. Lou et al [
7] performed 24 double-shear tests on precast concrete insulated sandwich panels using stainless-steel plate connectors. Authors analysed parameters like connector directions, insulation effect, cavity widths and connector heights. Authors developed a consisted campaign with in-plane and out-of-plane shear test and concluded that the cavity size and the presence of insulation significantly contributed to shear transfer. Choi et al. [
8] analysed some precast concrete sandwich panels used for exterior cladding. Specimens were experimentally tested with push-out test, with and without corrugated shear connectors. The investigation of the in-plane shear performance showed a relevant impact of the core material in the structural response. And later, Choi et al. [
9] extended the study of the shear flow over type of connectors. There are other relevant contributions about the shear performance of sandwich insulation panels using other types of test like Sylaj et al [
10], Hou at al [
11], Meng et al. [
12] or Wang et al. [
13].
To advance towards the utilization of more sustainable materials compared to synthetic fibres and steel, the present study concentrates on the creation of sandwich panels comprising vegetal FRCM and expanded polystyrene as insulation. Authors have previously presented other complementary studies about FRCM vegetal fibres, see Mercedes et al. [
14] and [
15] and some bending test for sandwich FRCM solutions, see Mercedes et al [
16]. For the present work the innovation lies in the use of vegetal FRCM skins and the introduction of flexible connectors made from vegetal fibres. Connection between layers is a must to have the necessary mechanical properties to develop composite materials that are competent with those commonly used in the construction industry. In this study, sandwich specimens were created using different fabrics (hemp, sisal, and glass) and connectors (hemp, sisal, and steel). These specimens underwent a double shear test to examine how these fabrics and connectors influence the panel's strength against shear. Additionally, simplified connector slip-load model is developed and compared to the experimental results.
2. Materials and Methods
The experimental campaign includes the manufacturing of specimens of FRCM bonded to an extruded polystyrene core and shear tests. These specimens were produced using next specific procedures and materials.
2.1 Mortar
To manufacture the FRCM component, a thixotropic commercial mortar was used. This mortar is a single-component mixture comprising cement, synthetic resins, and polyamide fibers, with the addition of silica fume. The choice of this mortar was based on its proven effectiveness in previous studies Mercedes et al. [
15]. The average results of the compression and flexion tests using norm EN1015-11:2000 [
16] has been previously presented in the cited work with values of 39.25 MPa and 6.56 MPa respectively.
2.2 Fabrics
Two type of vegetal fabrics and another one of synthetic fibres were used to manufacture the FRCM part: Hemp, sisal and glass (contrast material).
Vegetal fabrics were crafted using hemp and sisal yarns (both with diameter of 2.5 mm). This arbitrary choice is justified by the notable tension levels achieved by hemp and sisal FRCM specimens in a prior study by Mercedes et al. [
17]. In that study, the fabrics and yarns were coated with epoxy resin. This was done to prevent fibre degradation produced by the environment of cementitious matrix composites (high alkalinity and humidity cycles), see Ardanuy et al. [
18].
The size of the free cells in the grids of vegetal fabrics was determined by referencing the geometry of a commercial glass fabric (see
Figure 1). In the case of vegetal fabrics, it was necessary to craft the meshes with greater volume of material to achieve the load capacity of glass fabrics, producing thicker meshes than synthetic ones. Two yarns were utilized for each tuft, underscoring that tensile strength and effectiveness were comparable to synthetic fiber meshes just by simply increasing the volume of vegetal fibers.
Weft yarns of hemp and sisal fabric were made of hemp yarns of 0.5 mm in order to reduce the thickness of the weft and wrap crossing point, and because the load capacity in weft direction is no relevant for the shear test setup used in this study.
The fabrics were woven (
Figure 2) with the same procedures used in Donnini et al [
19] and D’Antino et al. [
20]. After one day of curing, the meshes were cut into pieces with dimensions of 45 mm × 35 mm.
The mechanical properties of the tuft (two yarns in the vegetal fabrics case) are shown in
Table 1. The coated tuft data were obtained experimentally in this study using the tensile test procedure using norm EN ISO 13934-1/2 [
21].
2.3 Connectors
To assess the impact of connectors on the shear behavior of FRCM bonded to an ex-truded polystyrene core, connectors of hemp, sisal and steel were used. Hemp and sisal were selected as they are the vegetal fibers used in this study for crafting vegetal fabrics, while steel was chosen as it is the most commonly commercial material used for connector in such types of sandwich solution.
Vegetal fibre connectors were crafted hook-shaped and impregnated with epoxy resin, featuring an equivalent area of 29.43 mm2 (6 yarns). Steel connectors were in the shape of a pin or bolt with a cross-sectional area of 0.79 mm2, accompanied by a nut at one end to enhance anchoring effect with the mortar (see
Figure 3).
2.4 Extruded polystyrene
Rigid Extruded Polystyrene foam boards with a thickness of 40 mm were used as the insulating core in the sandwich samples configuration.
2.5 Specimens
The experimental program included 40 specimens. The dimensions of the FRCM were of 50×400 mm and a thickness of 20 mm. These 40 samples included 3 different con-nectors (steel, hemp and sisal) and 3 different reinforcement fabrics (hemp, sisal and glass).
The mold to manufacture the FRCM specimens were prepared with a grid of wooden strips defining 50 mm x 400 mm gaps (see
Figure 4). These strips had a height of 20 mm. The manufacturing procedure was as follows:
Prepare the mold base with a demolding agent.
Mix the mortar and pour it to a depth of approximately 15 mm.
Place the fabric so that it slightly penetrated the first mortar layer.
Cover the fabric with a second layer of mortar to reach the thickness of 20 mm for the bottom FRCM layers.
Place the extruded polystyrene boards. In the case of specimens with connectors it had a hole in the middle.
Place other wooden strips mold (without a base) in the same location as the first mold.
Add a third layer of mortar to reach the final thickness.
Place the second fabric so that it slightly penetrated the first layer of mortar.
For panels with connectors, place the connectors so that the top is above the fabric.
Cover the second fabric (and connectors) with a fourth layer of mortar to reach the thickness of 20 mm for the top FRCM layers.
Demold and leave samples to cure in laboratory conditions for 28 days. After this period, the specimens were ready for testing.
The nomenclature used to identify the specimens is provided in
Table 2.
3. Experimental campaigns
3.1 Test setup and instrumentation
The specimens were subjected to a double shear test (see
Figure 5). In this test, metal plates (similar to those used in tension tests) were bonded to one end of the FRCM on each side of the sandwich specimen. This shear test is an adaptation inspired by the tension test with the clevis system according AC434-0213-R1 [
22]. In this configuration, auxiliary plates of aluminum were attached externally on opposite sides of the load application, simply to prevent the turning of the specimens during the test. The test rate was 2 mm/min.
3.2 Type of failures
In general, all the specimens had a peeling failure because polystyrene is a low strength material. Nevertheless, in the case of the samples with connectors, there was also a slip-page of the connectors accompanied by the detachment of the mortar in the connector area, in some cases. Consequently, specimens with connectors displayed more cracking and ductile failure compared to the sudden and brittle failure observed in specimens without connectors (
Figure 6).
3.3 Experimental results
Table 3 shows the experimental results of maximum load and shear stress (Fmax and τmax), the elastic stiffness (Ke) and shear modulus (Ge), obtained from the lineal stage in the load-displacement diagrams. Also, table present the displacement (δmax) and angular distortion (δmax/te) at the maximum load. Where te is the distance (60mm) between the fabric embedded in the FRCM skins. To calculate the shear stress and shear modulus was used the shear value from the FRCM skin dethatched (50×250mm).
The results in Table 4 show coefficients of variation ranging between 2 and 14% for maximum load and shear strength, indicating good repeatability of the experiments. It is noteworthy that specimens without connectors presented similar shear strength. However, for stiffness and displacements the variation was higher, ranging between 7 and 47%. This variablity represents the expected scattering of data for elements composed of cementitious materials with a high no lineal behavior. The results presented in Table 4 are better appreciated in
Figure 7 and
Figure 8.
Figure 7 shows the impact of the fabric on the maximum load and elastic stiffness of the specimens. The performance of different fabric types remains consistent for both maximum load and stiffness values, regardless of the presence of connectors. Concerning maximum load, the inclusion of connectors significantly enhances capacity for vegetal specimens, ranging from 13% to 53%. However, there is no notable change for glass fabric. This suggests that the FRCM skin may not reach the cracking strength required to activate the glass fabric, unlike what occurs with vegetal fabrics. Nevertheless, connectors play a beneficial role in maintaining cohesion between materials, activating vegetal fabrics at the achieved level of strain until significantly produce a higher ultimate load.
In terms of elastic stiffness, the response of the FRCM sandwich is directly tied to the Young modulus of the fabric—stiffer fabric correlates with higher specimen stiffness. Despite glass fabric being seven times stiffer than hemp fabric, this stiffness difference is not prominently reflected in the specimens. This is due to the initiation of non-linear behavior in the core deformation for low values of FRCM strain, minimizing the activation of fabric capacity in the composite and resulting in negligible stiffness differences.
Connectors prove efficient in ensuring strain compatibility among components, leading to an increase in stiffness values ranging from 11% to 40%. Although the influence of connectors during the elastic phase is minimal compared to the effect over the ultimate load, they play a crucial role in maintaining overall specimen compatibility.
Figure 8 illustrates the impact of the type of connector on the maximum load and on elastic stiffness for the hemp fabric specimens. The presence of connectors, independently of their material, increases both the maximum load and the elastic stiffness. Steel connector reaches the highest load and the highest stiffness. Therefore, the presence of stiff connectors maintains the strain field and the compatibility between layers in a more efficient manner than flexible vegetal connectors. The difference of stiffness between the fabric and the steel connector seems not to be a handicap, even thought that some local damage happens in the mortar because of the concentration effects of steel bolt.
Figure 9 shows the load-displacement plots of the tested panels. It can be seen that specimens without connectors exhibit a quasi-brittle failure with limited range of deformation (dashed lines) compared to specimens with connectors (continuous line). The presence of connectors enhances the activation of vegetal fabrics, effectively tightening the interfaces between materials and contributing to an increased strength of the sandwich structure. In the case of glass, the levels of strain are low in the FRCM and the fabric is not activated, therefore there is no large difference in the load-displacement plots.
4. Connectors interlock-slip simplified model
According the experimental results, it is worth to build a simple model to easily pre-dimension solutions for FRCM sandwich panels. Therefore, it is necessary to estimate the contribution of the connectors to the response of the structure. The problem is very complex involving nonlinear behavior of FRCM skins, interface interaction among materials and debonding and slipping failure. A real model is far from the scope of the contribution. Nevertheless, a rough approach might take advantage of the comparison between the response of specimens without connectors and the ones with connectors. Therefore, in a simply manner:
From Table 5 and plots of
Figure 9 (a, b and c) it is feasible to estimate the contribution of the interface of FRCM and polystyrene. To study the effect of the connector, only hemp FRCM specimens (SH) were used because contains all type of samples.
The connectors collaborate performing a bi-linear behavior. Each one collaborates increasing its contribution until the maximum load is reached, while after, they are capable of maintaining it without a significant reduction, due its stiffness.
As stated in
Figure 8, steel connectors showed the highest stiffness, followed by hemp and finally sisal ones. This property explains the reason why steel connectors are the ones that contribute more significantly to the shear strength of the specimen, providing a contribution 165% more than the vegetal connectors. Hemp and sisal show a similar contribution, due its similar mechanical properties studied in
Table 2.
Therefore,
Figure 10 will make an estimation of the connector contribution.
5. Results
In this work, an experimental and numerical research was conducted to investigate the shear performance of sandwich specimen with vegetal-FRCM and polystyrene. According the achieved results:
All specimens experienced a peeling failure. However, specimens with connectors exhibited additional slippage of the connectors, resulting in more cracking and ductile failure compared to the fragile failure observed in specimens without connectors.
The results shown that there is no significant influence of the kind fabric in the maximum load of the specimen without connector. This happens because the FRCM skin do not reach the cracking level required for the fabric to be activated and effectively contribute to the strength.
In the case of the specimens with connectors the level of maximum loads and elastic stiffness were both increased. Vegetal fabrics were effectively activated by the cracking while glass was very little activated. Therefore, the comparative performance produced a more ductile response in vegetal fabrics.
All the type of connectors increased the maximum load and elastic stiffness of the sandwich specimens. The steel connector reached the highest maximum load and elastic stiffness. Hence stiff connectors produced a tightening effect between the layers of materials and the higher stiffness in connectors the higher sandwich response.
An interlock-slip model based on experimental evidences shows the potential to design FRCM solutions for sandwich applications with connectors.
Author Contributions
Conceptualization, L.M .; methodology, L.M..; software, E.B..; validation, L.G, E.B. formal analysis, L.M., investigation, L.M., E.B., V.M, L.G..; resources, L.G.; data curation, L.G..; writing—original draft preparation, L.B.; writing—review and editing, L.G, E.B., V.M..; visualization, L.M, V.M..; supervision, L.G. E.B.; project administration, L.G.; funding acquisition, L.G. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the research project ‘‘Investigación para la impresión 3D de compuestos aislantes de FRCM para cerramientos inteligentes en edificación" COMPI3D’’, PID2022-137156OB-I00. It is funded by Agencia Estatal de Investigación (AEI), Ministerio de Ciencia e Innovación.
Data Availability Statement
Data acquired are directly presented in plots being original and not inappropriately selected, manipulated, enhanced, neither fabricated.
Acknowledgments
The materials were supported by Sika AG and Mapei Spain S.A. Fourth author is a Serra Húnter Fellow.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- Thainá Faria Oliveira, José Maria Franco de Carvalho, Júlia Castro Mendes, Ga-briela Zuqui Souza, Victor Rezende Carvalho, Ricardo André Fiorotti Peixoto, Precast concrete sandwich panels (PCSP): An analytical review and evaluation of CO2 equivalent, Construction and Building Materials, ISSN 0950-0618, Volume 358, (2022), 129424. 0950. [CrossRef]
- Pablo Resende Oliveira, Michael May, Tulio Hallak Panzera, Stefan Hiermaier, Bio-based/green sandwich structures: A review, Thin-Walled Structures, ISSN 0263-8231, Volume 177, (2022), 109426. A. [CrossRef]
- B. Cox, P. Syndergaard, S. Al-Rubaye, F.F. Pozo-Lora, R. Tawadrous, M. Maguire, Lumped GFRP star connector system for partial composite action in insulated precast concrete sandwich panels, Composites Structures, ISSN 0263-8223, Volume 229, (2019), 111465. [CrossRef]
- N.W. Portal, K. Zandi, K. Malaga, L. Wlasak, GFRP connectors in textile reinforced concrete sandwich elements, IABSE Congr. Stock. 2016 Challenges Des. Constr. an Innov. Sustain. Built Environ. (2016) 1336–1343. 1336–1343.
- T. Hulin, K. Hodicky, J.W. Schmidt, H. Stang, Experimental investigations of sandwich panels using high performance concrete thin plates exposed to fire, Materials and Structures. ISSN 1359-5997, Volume 49, (2016), 3879–3891. [CrossRef]
- D.G. Tomlinson, N. Teixeira, A. Fam, New Shear Connector Design for Insu-lated Concrete Sandwich Panels Using Basalt Fiber-Reinforced Polymer Bars, Journal of Composite Construction. ISSN 1943-5614 , Volume 20, (2016) 04016003. [CrossRef]
- Xiaohang Lou, Weichen Xue, Haoyang Bai, Ya Li, Qian Huang, Shear behavior of stainless-steel plate connectors for insulated precast concrete sandwich panels, Structures, ISSN 2352-0124, Volume 44, (2022), Pages 1046-1056. [CrossRef]
- Ki-Bong Choi, Won-Chang Choi, Luciano Feo, Seok-Joon Jang, Hyun-Do Yun, In-plane shear behavior of insulated precast concrete sandwich panels reinforced with corrugated GFRP shear connectors, Composites Part B: Engineering, ISSN 1359-8368, Volume 79, (2015), Pages 419-429. E. [CrossRef]
- Wonchang Choi, Seok-Joon Jang, Hyun-Do Yun, Design properties of insulated precast concrete sandwich panels with composite shear connectors, Composites Part B: Engineering, ISSN 1359-8368, Volume 157, (2019), Pages 36-42. [CrossRef]
- Valon Sylaj, Amir Fam, UHPC sandwich panels with GFRP shear connectors tested under combined bending and axial loads, Engineering Structures, ISSN 0141-0296, Volume 248, (2021), 113287. [CrossRef]
- Hetao Hou, Wenhao Wang, Bing Qu, Chunxue Dai, Testing of insulated sand-wich panels with GFRP shear connectors, Engineering Structures, ISSN 0141-0296, Vol-ume 209, (2020), 109954. [CrossRef]
- Yan Meng, Wang Lian-guang, Chen Bai-ling, Shear resistance and deflection prediction of steel–concrete–steel sandwich panel with headed stud connectors, Structures, ISSN 2352-0124, Volume 54, (2023), Pages 1690-1704. [CrossRef]
- Yonghui Wang, Junyi Chen, Ximei Zhai, Xudong Zhi, Hongyuan Zhou, Static behaviours of steel-concrete-steel sandwich beams with novel interlocked angle connectors: Test and analysis, Journal of Constructional Steel Research, ISSN 0143-974X, Volume 201, (2023), 107723. [CrossRef]
- Luis Mercedes, Virginia Mendizábal, Ernest Bernat-maso, Lluis Gil, Performance of hemp-FRCM-strengthened beam subjected to cyclic loads, Materiales de Construcción, ISSN-L: 0465-2746, Vol. 72, 345, January-March (2022), e270. [CrossRef]
- Luis Mercedes, Lluis Gil, Ernest Bernat-Maso, Mechanical performance of vegetal fabric reinforced cementitious matrix (FRCM) composites, Construction and Building, ISSN 0950-0618, Materials, Volume 175, (2018), Pages 161-173. [CrossRef]
- EN 1015-11. “Methods of test for mortar for masonry. Part 11: Determination of flexural and compressive strength of hardened mortar”. 2019.
- Luis Mercedes, Ernest Bernat-Maso, Lluís Gil, Bending and compression perfor-mance of full-scale sandwich panels of hemp fabric reinforced cementitious matrix, Engineering Structures, ISSN 0141-0296, Volume 275, Part B, (2023), 115241. [CrossRef]
- Mònica Ardanuy, Josep Claramunt, Romildo Dias Toledo Filho, Cellulosic fiber reinforced cement-based composites: A review of recent research, Construction and Building Materials, ISSN 0950-0618, Volume 79, (2015), Pages 115-128. [CrossRef]
- Jacopo Donnini, Valeria Corinaldesi, Mechanical characterization of different FRCM systems for structural reinforcement, Construction and Building Materials, ISSN 0950-0618, Volume 145, (2017), Pages 565-575. [CrossRef]
- T. D'Antino, Catherine Papanicolaou, Mechanical characterization of textile reinforced inorganic-matrix composites, Composites Part B: Engineering, ISSN 1359-8368, Volume 127, (2017), Pages 78-91. [CrossRef]
- BS EN ISO, ‘‘Textiles–Tensile properties of fabrics - Part1: Determination of maximum force and elongation at maximum force using the strip method,” no. EN ISO 13934-1/2, 2013.
- ICC Evaluation Service Inc., ‘‘Proposed Revisions to the Acceptance Criteria for Masonry and Concrete Strengthening Using Fiber-reinforced Cementitious Matrix(FRCM) Composite Systems, Subject AC434-0213-R1(ME/BG),”2012.
|
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).