In this section, the proposed PSO - POED algorithm was applied to optimally tune the parameters of the AVR and , and of the PSS of the synchronous generators of the SMIB and IEEE 9-bar test systems, keeping the values of the other parameters constant: , and . The results are compared with those obtained by applying the alternative optimization algorithms PSO - LD, PSO - OIW and PSO - OED. The following simulation parameters were used in all algorithms: Maximum number of iterations = 100, , , , and . Regarding the number of particles, for the Infinite Bar Machine System (SMIB) 50 particles were used, while for the IEEE 9-bar System 100 particles were used.
6.2. Case Study of the 9-Bus Multi-Machine System
This system is made up of three synchronous hydraulic generators: G1 (
slack), G2 and G3, as seen in
Figure 11.
Generators G2 and G3 produce a voltage at their terminals of 1.025 p.u and 1.026 p.u respectively. In the 9-bar IEEE System, a disturbance occurs in the first second of operation, which is cleared after 100 ms. This disturbance consists of a short circuit near the line L5-7, which produces an increase in current and a drop in voltage of the generators. By action of the controllers, this voltage level is brought back in 1ms to the voltage values produced prior to the disturbance. However, some oscillations occur in this recovery, which need to be corrected in the best way to avoid damage to the Power System, which is achieved through adequate tuning of the AVR and PSS parameters.
For the IEEE 9-bar System, when using the proposed PSO - POED algorithm, the best values found for the parameters are:
Cycles = 4, = 10, M = 20
Figure 12 shows the Time Response Analysis of the voltage signal of the generator G2 after the short circuit disturbance, which was corrected by the action of the proposed PSO - POED algorithm with which the controller parameters were tuned. The Set Point is the voltage at the terminals of the generator G2.
Figure 12 shows that the maximum peak of the voltage signal corrected by the proposed PSO - POED algorithm is 1.046 p.u., therefore the maximum overshoot (
) is:
Additionally, it is observed that the signal keeps into the error band since the second peak, whose value is 1.0362. The steady state error () is the difference between this value and the set point (1.025), giving the value of 0.0112%.
In
Figure 12 the lower dashed red line marks 10% of the final value, while the upper dashed red line marks 90% of the final value. Once these values have been identified, it follows that the rise time (
) of the signal is 0.2617s, since this value is the difference between the instant in which the signal crosses the set point and the time at which the signal appears.
The admissible tolerance to consider that the system is in steady state is assigned to 2%, therefore the band that indicates that the response signal remains in this state is defined by the upper limit (
) and lower limit (
), as seen in
Figure 12, which are obtained according to:
Knowing these values, the settling time () of the response signal is 0.3017s because this value is the difference between the time in which the signal enters and remains within the error band, which occurs in the second peak, and the emergence of the signal.
Similarly, alternative algorithms variants of the classic PSO were applied in order to evaluate their performance and compare the results obtained with the proposed algorithm.
Figure 13 shows the response signals to the disturbance applying the alternative algorithms and the proposed PSO - POED algorithm.
Figure 13 shows that the signal of the proposed PSO - POED algorithm is the fastest, since it reaches the reference first, so its rise time (
) is the shortest among the four algorithms. Likewise, it is observed that the signal of the proposed PSO - POED algorithm presents the lowest maximum overshoot value (
), the shortest settling time (
) and the lowest steady state error (
)
In a similar way, this analysis is carried out for the G3 generator of the 9-Bus Multi -Machine Power System.
Figure 14 shows the Time Response Analysis of the voltage signal of the generator G3 after the short circuit disturbance, which was corrected by the action of the proposed PSO - POED algorithm with which the parameters of its controllers were tuned.
Figure 14 shows that the maximum peak of the voltage signal corrected by the proposed PSO - POED algorithm is 1.047 p.u., therefore the maximum overshoot (
) is:
Additionally, it is observed that the steady state error () is: 0.0077%.
Similarly, in
Figure 14 the lower red dashed line marks 10% of the final value, while the upper dashed red line marks 90% of the final value. Once these values have been identified, it follows that the growth time (
) of the signal is 0.242s.
Considering 2% as the admissible tolerance value for the system to be in steady state, the upper (
) and lower (
) limits are calculated according to:
Knowing these values, the settling time () of the response signal is 0.2817s.
Similarly, alternative algorithms variants of the classic PSO were applied in order to evaluate their performance and compare the results obtained with the proposed algorithm.
Figure 15 shows the response signals to the disturbance applying the alternative algorithms and the proposed PSO - POED algorithm.
Figure 15 shows that the signal of the proposed PSO - POED algorithm is the fastest, since it reaches the reference first, so its growth time (
) is the shortest among the four algorithms. Likewise, it is observed that the signal of the proposed PSO - POED algorithm presents the lowest maximum overshoot value (
), the shortest settling time (
) and the lowest steady state error (
).
The parameters of the AVR and PSS controllers are tuned to values within established ranges. These limits for both controllers are shown in Table 4.
Table 4 shows that the established limits are different from those indicated in
Table 1, this is because the SMIB System has a thermoelectric generator, while in the 9-bar IEEE System the generators are hydraulic.
Table 5 shows the AVR and PSS parameters obtained by applying the proposed algorithm and the alternative algorithms, which were also applied in this paper for comparison purposes. Likewise, the convergence results for the 100 simulations carried out using the different algorithms are shown.
Table 5 shows that the proposed algorithm (PSO - POED) is superior in several aspects to the alternative algorithms (PSO - LD, PSO - OIW and PSO - OED), mainly by observing the best result obtained from the 100 simulations (Best), as well as the worst and the average result (Worst and Average, respectively), which turns out to be greater than the others. The value of the standard deviation (Stand.Dev.) obtained by using the PSO - POED is higher than the others because the results obtained are significantly high. In fact, the worst solution found by PSO - POED far exceeds the better solutions from the other algorithms.
Table 6 shows the values of the parameters of the voltage signal of the generators in the Time Response Analysis, which were obtained by applying the different algorithms.
Table 6 shows that by applying the proposed algorithm (PSO - POED), better values are obtained for the parameters of rise time (
), settling time (
), steady state error (
) and peak overshoot (
) than when applying the alternative algorithms (PSO - LD, PSO - OIW and PSO - OED), which is true for both synchronous generators.